Power Module Replacement
The SMART3000RMOD2U features a hot-swappable power module. There is no manual bypass switch on the unit. However, when the bracket holding the power module in
place is removed (see Step #3 below), the UPS will automatically switch to "BYPASS" mode, allowing the power module to be removed for maintenance, repair or replace-
ment without disrupting power to connected loads. While the UPS is in "BYPASS" mode, connected equipment will receive unfiltered AC mains power, but the equipment
will not receive battery power in the event of a blackout. NOTE: Do not turn off the UPS when removing the power module. Doing so will turn off the rear output. Do
not remove the power module while operating from battery power.
Step 1: Remove front panel
A
Step 2: Disconnect battery connectors
Step 3: Remove the screws that hold power
module in place. Remove smaller bracket
covering bypass switch
C
.
Step 4: Remove power module
Step 5: Add new power module
Step 6: Replace the bypass switch bracket
and replace screws to secure power module to
UPS.
Step 7: Connect battery connectors
connectors black-to-black and red-to-red.
Step 8: Replace front panel
A
Step 9 (Not shown): Press "On" button until
unit beeps.
201112106 93-2729.indb 12
.
B
.
D
.
D
.
C
B
. Attach
.
A
1
B
2
C
3
4
12
8
7
6
D
5
12/28/2011 3:44:16 PM