INSTALLATION
4
Addition of refrigerant ( long pipes )
If the connection pipe has a length greater than 7 metres, a refrigerant should be
If the connection pipe has a length greater than 7 metres, a refrigerant should be
If the connection pipe has a length greater than 7 metres, a refrigerant should be
If the connection pipe has a length greater than 7 metres, a refrigerant should be
added. Make-up quantity A=(Lm-7m) x 15g/m.
Length of connection pipe (m)
Make-up quantity (g)
• Connect the bottle of refri-
gerant gas to the gas supply
orifice (do not tighten the
gas pipe screw on the gas
closing valve).
• Open the valve of the gas
bottle and purge the air from
the units with the gas.
• When the gas can be seen
at the connection in the
form of mist, tighten the
connection.
• On the scale, read the wei-
ght of gas to be added.
EXTERNAL UNIT WATER FLOWS
EXTERNAL UNIT WATER FLOWS
EXTERNAL UNIT WATER FLOWS
EXTERNAL UNIT WATER FLOWS
When using the heating mode, the external unit
When using the heating mode, the external unit
When using the heating mode, the external unit
When using the heating mode, the external unit
condenses water. A hole is provided in its lower
condenses water. A hole is provided in its lower
condenses water. A hole is provided in its lower
condenses water. A hole is provided in its lower
part to allow evacuation of this water. It is also
part to allow evacuation of this water. It is also
part to allow evacuation of this water. It is also
part to allow evacuation of this water. It is also
possible to connect an emptying hose here (not
possible to connect an emptying hose here (not
possible to connect an emptying hose here (not
possible to connect an emptying hose here (not
supplied) in order to collect these flows (of the
supplied) in order to collect these flows (of the
supplied) in order to collect these flows (of the
supplied) in order to collect these flows (of the
order of 1 to 2 l/day depending on the humidity
order of 1 to 2 l/day depending on the humidity
of the air)
of the air).
112500-504-E
Intérnal unit
Dont rock the bottle during the supply operation.
Dont rock the bottle during the supply operation.
Dont rock the bottle during the supply operation.
Dont rock the bottle during the supply operation.
Dont rock the bottle during the supply operation.
Dont heat the bottle with fire or hot air.
Dont heat the bottle with fire or hot air.
Dont heat the bottle with fire or hot air.
Dont heat the bottle with fire or hot air.
Dont heat the bottle with fire or hot air.
© FAR GROUP EUROPE 2004
56
7
0
15 15
Liquids pipe
Liquids pipe
Liquids pipe
Liquids pipe
Liquids pipe
Liquids pipe
Liquids pipe
Liquids pipe
Valves
Valves
Valves
Gas pipe
Gas pipe
Gas pipe
Gas pipe
R407C
R407C
R407C
R407C
Hot water (~ 40°C )
Hot water (~ 40°C )
Bottom
Connection for double
channel emptying
24/01/05, 11:38
8 8
9
10
30
30
45
External unit