Beretta Ciao Green R.S.I. Serie Manual De Instalacion Y Uso página 10

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 18
CIAO GREEN R.S.I.
- loosen the fi xing screw then turn the instrument panel
- loosen the fi xing screws on the cover (F) to access the terminal board (fi g. 16)
- while the boiler is powered up, using a small screwdriver included, press
the CO button (fi g. 26) for at least 4 seconds, to check the meter has
been reset, power down then power up the boiler; the meter reading is
shown on the monitor after the "-C-" sign.
Live electrical parts (230 V AC).
Note: the meter resetting procedure should be carried out after each in-
depth cleaning of the primary exchanger or if this latter is replaced. To
check the status of the total hour meter, multiply the reading by 100 (e.g.
reading of 18 = 1800 total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A 77
This is an automatic-reset fault, if the boiler does not restart, contact the
Technical Assistance Centre.
Flashing yellow LED
Combustion analysis in progress.
4.4 Alarm records
The "ALARM RECORDS" function starts automatically once the display has
been on for 2 hours, or immediately by setting the P1 parameter to 1.
The records include all the latest alarms, up to a maximum of 5 alarms, and
they are displayed in sequence by pushing and releasing the P1 button on
the display board. If the records are empty (P0=0) or if tracking the same is
disabled (P1=0), the display function is not available.
Alarms are displayed in reverse order compared to the order in which they
occurred: this means that the last alarm generated is the fi rst to be display-
ed. To delete the alarms records, simply set parameter P0 to 0.
NOTE: To get to the P1 button the cover on the control panel must be remo-
ved and the display board must be identifi ed (fi g. 36a).
PROGRAMMING PARAMETERS
Functioning of the display can be personalised by programming three pa-
rameters:
Parameter
Default
P0
0
Deletion of alarms records
(0 = records empty / 1 = records not empty)
P1
0
Immediate activation of alarm record mana-
gement
(0 = delayed records management activated /
1 = immediate records management activated
P2
0
Do not change
When button P1 on the display (fi g. 36a) is held down for at least 10 sec,
the programming procedure is activated. The three parameters, with their
respective values, are shown in rotation on the display (fi g. 36b). To edit a
parameter value, simply push the P1 button again when the required para-
meter is displayed, and then hold it down until the value switches from 0 to
1 or vice-versa (approx. 2 sec).
The programming procedure is closed automatically after 5 minutes, or if
there is an electrical power failure
4.5 Boiler confi guration
There is a series of jumpers (JPX) available on the electronic board which
enable the boiler to be confi gured.
To access the board, proceed as follows:
- turn off the main switch on the system
- loosen the fi xing screws on the housing, move the base of the housing
forwards and then upwards to unhook it from the chassis
- undo the fi xing screws (E) from the instrument panel (fi g. 14)
- loosen the screws (F - fi g. 16) to remove the cover of the terminal board
(230V)
JUMPER JP7 - fi g. 37:
preselection of the most suitable heating temperature adjustment fi eld ac-
cording to the installation type.
Jumper not inserted - standard installation
Standard installation 40-80°C
Jumper inserted - fl oor installation
Floor installation 20-45°C.
In the manufacturing phase, the boiler is confi gured for standard installations.
JP1
Calibration (Range Rated)
JP2
Reset heating timer
JP3
Calibration (see paragraph on "Adjustments")
JP4
Do not use
10
Description
JP5
Heating only function with a predisposition for external storage tank
with thermostat (JP8 inserted) or probe (JP8 not inserted)
JP6
Enable night-time compensation function and continuous pump (only
with external sensor connected)
JP7
Enable management of low temperature/standard installations (see
above)
JP8
Management of an external storage tank with thermostat enabled
(jumper inserted)/ management of an external storage tank with pro-
be (jumpers not inserted) fi g. 37.
The boiler foresees jumpers JP5 and JP8 inserted as standard (heating
only version arranged for storage tank with thermostat); if the use of an
exterior storage tank with probe is required, jumper JP8 must be removed.
4.6 Setting the thermoregulation (graphs 1-2-3)
The thermoregulation only operates with the external sensor connected;
once installed, connect the external sensor (accessory available on request)
to the special terminals provided on the boiler terminal board (fi g. 5).
This enables the THERMOREGULATION function.
Selecting the compensation curve
The compensation curve for heating maintains a theoretical temperature of
20°C indoors, when the external temperature is between +20°C and -20°C.
The choice of the curve depends on the minimum external temperature
envisaged (and therefore on the geographical location), and on the delivery
temperature envisaged (and therefore on the type of system). It is carefully
calculated by the installer on the basis of the following formula:
envisaged delivery T. - Tshift
KT=
20- min. envisaged external T.
Tshift =
30°C standard installations
25°C fl oor installations
If the calculation produces an intermediate value between two curves, you
are advised to choose the compensation curve nearest the value obtained.
Example: if the value obtained from the calculation is 1,3 this is between
curve 1 and curve 1,5. Choose the nearest curve, i.e. 1,5.
Select the KT using trimmer P3 on the board (see multiwire wiring diagram).
To access P3:
- remove the housing,
- loosen the fi xing screw on the instrument panel
- turn the instrument panel towards you
- loosen the fi xing screws on the terminal board cover
- unhook the board casing
Live electrical parts (230 V AC).
The KT values which can be set are as follows:
standard installation: 1,0-1,5-2,0-2,5-3,0
fl oor installation 0,2-0,4-0,6-0,8
and these are displayed for approximately 3 seconds after rotation of the
trimmer P3.
TYPE OF HEAT REQUEST
Boiler connected to room thermostat (JUMPER 6 not inserted)
The heat request is made by the closure of the room thermostat contact,
while the opening of the contact produces a switch-off. The delivery tem-
perature is automatically calculated by the boiler, although the user may
modify the boiler settings. Using the interface to modify the HEATING, you
will not have the HEATING SET-POINT value available, but a value that you
can set as preferred between 15 and 25°C. The modifi cation of this value
will not directly modify the delivery temperature, but will automatically affect
the calculation that determines the value of that temperature, altering the
reference temperature in the system (0 = 20°C).
Boiler connected to a programmable timer (JUMPER JP6 inserted)
With the contact closed, the heat request is made by the delivery sensor, on
the basis of the external temperature, to obtain a nominal indoor tempera-
ture on DAY level (20°C). With the contact open, the boiler is not switched
off, but the weather curve is reduced (parallel shift) to NIGHT level (16°C).
This activates the night-time function.
The delivery temperature is automatically calculated by the boiler, although
the user may modify the boiler settings.
Using the interface to modify the HEATING, you will not have the HEAT-
ING SET-POINT value available, but a value that you can set as preferred
between 25 and 15°C.
The modifi cation of this value will not directly modify the delivery tempera-
ture, but will automatically affect the calculation that determines the value
of that temperature, altering the reference temperature in the system (0 =
20°C for DAY level, and 16°C for NIGHT level).
4.7 Adjustments
The boiler has already been adjusted by the manufacturer during produc-
tion. If the adjustments need to be made again, for example after extraordi-
nary maintenance, replacement of the gas valve, or conversion from meth-
ane gas to LPG, observe the following procedures.
The adjustment of the maximum and minimum output, and of the maximum
Tabla de contenido
loading

Este manual también es adecuado para:

Ciao green 25 r.s.i.

Tabla de contenido