Installation
Wiring
1
Wiring
Connect the power wires to the switch and the fuse base
terminals and connect the ground wire to the ground terminal
block inside the enclosure. Refer to the National Electric Code
and all local codes for appropriate wire size and grounding
requirements. See chapter Cabling.
All cables must have 167 °F / 75 °C minimum rating.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
1/12 Installation | Instruction Bulletin EOH361K, EOH362K, EOH363K, 1SCC340029M1401 / A
Safety
switch size
Line side and
[A]
load side terminal lugs
Wire range
ALL
#14 - 2/0
2.5 - 70 mm
2
Wire strip length L
ALL
0.55 - 0.63 in
14 - 16 mm
Wire tightening torque
for Cu and Al cables
(wire size )
[lbs.in (#)]
[Nm (mm
30
35 (#14 -10)
3.9 (2.5 - 4)
60
45 (#6 - 4)
5.1 (10 - 16)
100
50 (#3 - 2/0) 5.6 (25 - 70)
30
40 (#8)
4.5 (6)
60
45 (#6 - 4)
5.1 (10 - 16)
100
50 (#3 - 2/0) 5.6 (25 - 70)
Ground bus
#14 - 2
2.5 - 35 mm
2
0.39 - 0.47 in
10 - 11.9 mm
Wire size / tightening torque
2
)]
Material
[# / lbs.in.]
[mm
Copper
8 / 40
6 / 4.5
8 / 40
6 / 4.5
4 / 45
16 / 5.1
Aluminium
6 / 45
10 / 5.1
6 / 45
10 / 5.1
4 / 45
16 / 5.1
2
/ Nm]