MAINTENANCE GENERAL
1.
Perform visual, electrical and mechanical inspections on a regular basis.
The environment and frequency of use should determine this. However,
it is recommended that checks be made at least once a year. We
recommend an Electrical Preventive Maintenance Program as described
in the National Fire Protection Association Bulletin NFPA No. 70B:
Recommended Practice For Electrical Equipment Maintenance (www.
nfpa.org).
2.
The lens should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the lens with a clean, damp cloth. If this is
not sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or
Duco #7 . Do not use an abrasive, strong alkaline, or acid cleaner. Damage
may result.
3.
Visually check for undue heating evidenced by discoloration of wires or
other components, damaged parts or leakage evidenced by water or
corrosion in the interior. Replace all worn, damaged or malfunctioning
components, and clean gasket seals before putting the luminaire back into
service.
4.
Electrically check to make sure that all connections are clean and tight.
Mechanically check that all parts are properly assembled.
5.
Check and re-torque all mounting hardware.
6.
To prevent heat build-up, remove dust from the LED housing using a soft
brush or air pressure.
DRIVER REPLACEMENT INSTRUCTIONS
1.
Based on the electrical ratings marked on the luminaire housing, one
of the following LED driver replacement kits by Eaton's Crouse-Hinds
is suitable. Check and verify which particular driver is provided based
on the catalog number, and order the exact replacement driver kit from
Eaton's Crouse-Hinds. Prior to installation, ensure the same model
number, voltage and amperage ratings for replacement match the original
driver ratings that came with the fixture.
Driver Model
Catalog Number
Number
EUC030S050DTM
ZPLA2-UNV1-DRIVER KIT
EUC060S105DTM
ZPLA4-UNV1-DRIVER KIT
2.
Be sure to de-energize the luminaire before performing any maintenance.
3.
Driver replacement requires removal of the driver cover (see Figure 13).
4.
Open the threaded wiring access cap (see Figure 8) and allow the cap to
hang by the lanyard.
5.
Disconnect the input wires (line in, neutral and ground).
6.
Disconnect the conduit or fittings from the driver cover entries.
7 .
Remove the ten (10) socket head cap screws and lock washers from the
driver cover using a 5mm hex wrench or bit.
8.
Ensure all driver cover screws have been removed.
9.
Remove the driver cover.
10. Disconnect the input and output leads of the old driver
(see Figure 13).
11.
Remove the two (2) screws that secure the driver;
remove the old driver.
12. Unscrew the ground screw with a hex head bit, remove
the terminal ring and then remove the driver.
13. Remove thermal pad associated with old driver.
14. Replace with the new driver kit supplied by Eaton's Crouse-Hinds.
15. Peel off one side of the thermal pad and stick it to the bottom of the new
driver supplied by Eaton's Crouse-Hinds. After peeling off other side of
thermal pad, assemble the driver onto the housing. Assemble the ring
terminal, attached the ground wire of the driver with the ground screw,
and screw it in.
16. Reconnect output wires per wiring diagram. Ensure that the positive (+)
and negative (-) leads of the drivers are connected per the wiring diagram.
17 .
Re-install the new driver into the luminaire, ensuring that the driver is in
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not
guaranteed. In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Electrical Ratings Marked On
Compatible
Luminaire Housing
Fixture
V
Hz
120-277 VAC
50/60
ZPLA2-UNV1
127-300 VDC
50/60
120-277 VAC
50/60
ZPLA4-UNV1
127-300 VDC
50/60
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2020
direct contact with the luminaire housing and no wires are being pinched
between the driver and the housing. Secure with two (2) screws and
tighten to 6 in.-lbs. (0.7 N-m).
18. Ensure that output wires to LED boards are tied neatly next to the driver
and the input and dimming wire leads are tied neatly together (see Figure
13).
19. Reinstall the driver cover, ensuring no wires are being pinched between
the driver cover and the luminaire housing.
20. Re-install the ten (10) socket head cap screws and lock washers from the
driver cover using a 5mm hex wrench or bit.
21. Replace any damaged or missing cover screws. Use only alloy steel M6-
1.5 x 20mm screws.
22. Tighten cover screws in a criss-cross pattern and torque to 45 in.-lbs.
23. Reconnect the conduit or fittings to the driver cover entries.
24. Reconnect input wires per wiring diagrams.
25. Re-install threaded access cap (see "Wiring the Lighting Fixture").
Figure 12
PAINT SHIELD INSTALLATION INSTRUCTIONS
ZPLA PS2 and ZPLA PS4 accessories are paint shields that can be installed by
the
customer over the lens of the ZPLA to minimize paint overspray accumulation
on the light emitting surface.
1.
Ensure all previous installation steps have been followed.
2.
Locate the shield over the light emitting surface with the open portion
facing the luminaire (see Figure 14).
3.
Hook one side of the shield over the flange on one side of the luminaire
housing.
4.
Push on the opposite side of the paint shield to snap it over the flange on
the luminaire housing.
Paint Shield
REPLACEMENT PARTS
Eaton's Crouse-Hinds series linear LED fixtures are designed to provide years
of reliable lighting performance. However, should the need for replacement
parts arise, they are available through your authorized Eaton's Crouse-Hinds
distributor. Assistance may also be obtained through your local Eaton's Crouse-
Hinds representative or the Eaton's Crouse-Hinds Sales Service Department,
1201 Wolf Street, Syracuse, New York 13208, Phone 866-764-5454.
Figure 13
Figure 14
IF 1910
Revision 1
Revised 02/20