Always discount the pump from the electrical power source before handling. If the system fails
WARNING
to operate properly, carefully read instructions and perform maintenance recommendations. If
operating problems persist, the following chart may be of assistance in identifying and correcting them.
SYMPTOM
Pump runs but does
not pump liquid
Red light comes on
at control box
Overload trips at control
box and alarm due to high
water level in basin
Circuit breaker trips
overload protection
Grinder Pumps
Model: AGP-HC200 Series
Trouble Shooting
POSSIBLE CAUSES
1. Pump impeller maybe air locked
2. If pump is three phase, rotation may
be backward
3. Vent hole clogged
4. Clogged inlet
5. Discharge gate valve may be closed
6. Discharge check valve may be clogged
or have a broken clapper
7. Discharge head may be too high
1. This indicates some water has leaked
past the lower seal and has entered the
seal chamber and made contact with
the electrode probe
1. Grinder impeller may be clogged
with foreign objects
1. Excessive load possibly caused by a
short in the motor or control box.
2. If this condition happens after an
electrical storm, motor or control box
may be damaged by lightning
12
CORRECTIVE ACTION
1. Purge air
2. See instruction for checking
3. Clean out the vent hole
4. Clean out the grinder inlet
5. Open gate valve
6. Remove and examine check
valve for proper installation and
freedom of operation
7. Check elevation
1. Change oil in seal chamber,
find and repair cause of leak
1. Check grinder impeller for
freedom of operation, security
and condition. Clean impeller
cavity and inlet of any
obstruction
1. Check pump for short using
ohm meter
2. Reset breaker by pushing
completely down on handle
then back to ON position. If
breaker trips again in a few
seconds check motor for
lightning damage