Gate section limit stops on the ground

Check for the presence of the gate section limit stops J on the ground.
For the motor drive unit to operate correctly, using limit stops on the ground is required for both the opening and closing
directions.
The ends stops in the ground apply physical pressure to the gate leaves, thus limiting the mechanical stress on the
cylinders (particularly in windy conditions).

Electrical connections

Make the connections between the motor drive unit and the Control Box 3S Ixengo electronic controller for Ixengo L 24 V
and FX 230 electronic controller for Ixengo L 230 V.

ADJUstING tHE LIMIt stOPs - IXENGO L 24 v

The limit stops are adjusted by correctly positioning the motor drive unit limiting devices after first starting up the Control
Box 3S Ixengo electronic controller.
Important: For the 230 v motor drive unit, refer to the instructions on the FX 230 electronic controller and adjust
the time that the motor operates.

Adjusting the Fc1 closing limit stop

[1] Slacken the mounting screw K on the limit stop.
[2] Perform a closing cycle to check precisely where the limit stop takes effect.
[3] The motor stops when the edge of the end limit and the edge of the magnet
are aligned (i.e. when the magnet conceals the end limit).
[4] If the gate section does not close completely, slightly move the limit stop
towards the head cap L.
[5] If the gate section hits the limit stop on the ground when closing, the motor
drive unit reverses direction. Move the limit stop slightly towards the motor
drive unit's body.
[6] After correctly defining the limit stop's position, tighten down screw K.
[1]
8
[3]
K
[6]
L
Copyright © 2008 Somfy SAS. All rights reserved.