Rotex RKHBRD011ABV1 Manual De Instalación página 77

Unidad interior para bomba de calor de aire-agua
Ocultar thumbs Ver también para RKHBRD011ABV1:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 223
Remote controller room temperature control
When the reheat temperature is reached, the further heat up till
storage temperature of the domestic hot water tank will be decided
by the remote controller room thermostat in order to prevent the room
temperature to drop too much.
1
Reheat operation
When requesting space heating and domestic water heating
(reheat) at the same time, the domestic water will be heated till
maximum reheat temperature, then space heating will start
again.
K
E
D
J
C
H
B
A
A
Operation
Space heating
Domestic water heating
B
Domestic hot water reheat thermo-on request
C
Domestic hot water tank temperature
D
Room temperature thermo-on request
E
Remote controller room temperature
F
Domestic hot water lower limit temperature
G
Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H
Domestic hot water reheat minimum temperature [b-00]
J
Domestic hot water reheat maximum temperature [b-01]
K
Remote controller thermostat set point
ON
ON
OFF
OFF
RKHBRD011~016ABV1+Y1
Indoor unit for air to water heat pump system
4PW61218-1C – 2012.06
2
Storage operation
When requesting space heating and domestic water heating
(storage) at the same time, domestic water will be heated, but as
soon as the room temperature drops 3°C from set point, space
heating will start till 0.5°C above set point, then domestic water
will be heated again till storage set point.
K
E
+0.5°C
D
–0.5°C
–3.0°C
C
J
ON
H
OFF
G
75°C
B
A
F
35°C
ON
OFF
A
B
C
D
E
F
G
H
J
K
ON
OFF
1
2
3
4
5
6
(a) The minimum operation time is only valid when room temperature is more
(b) The maximum operation time is only valid when room temperature is more
1
3
6
2
5
Operation
Space heating
Domestic water heating
Domestic hot water storage thermo-on request
Domestic hot water tank temperature
Room temperature thermo-on request
Remote controller room temperature
Domestic hot water lower limit temperature
Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
Domestic hot water reheat minimum temperature [b-00]
Domestic hot water reheat maximum temperature [b-01]
Remote controller thermostat set point
ON
OFF
Minimum operation time for domestic water heating
(a)
(initial 10 minutes [d-00])
Maximum operation time for domestic water heating
(b)
(initial 30 minutes [d-01])
Interval minimum stop time for domestic water heating
(initial 15 minutes [d-02])
No simultaneous operation
Timers for domestic water heating start
Timer for space heating start
than 3°C lower as set point and set point J is reached.
than 0.5°C lower as set point and set point J is reached.
+0.5°C
–0.5°C
–3.0°C
ON
OFF
G
75°C
F
35°C
ON
OFF
4
Installation manual
28
Tabla de contenido
loading

Tabla de contenido