Fit the valve on the unit at the level of the swivel
couplings. The valve is installed at the unit's water
outlet.
Install the thermal actuator on the valve and
connect the cable in the electrical box as shown in
GB
the electric wiring diagram.
Mount the auxiliary tank (supplied with the unit) on
the side, below the valve.
House the tank's fitting in the hole underneath the
valve.
Secure the tank with the two screws provided.
B -Valve distant from the unit's hydraulic connections
• The valve can be installed on a pipe (not supplied) enabling it to be offset from the unit's hydraulic
connections.
In this case, place the valve along the unit, on the side perpendicular to the electrical box, so that it is above
the auxiliary tank.
VALVE KIT - CODE 70600089 - CWX6-8-10
• The valve kit includes:
- the valve body,
- 2 swivel couplings,
- 4 adapter couplings,
- actuator (with 230V "On / Off" heating element).
Assembly
A -Valve
directly
connections
• Fit the 3/4" male - 1/2" female adapter couplings on
the unit's female connectors, then screw the "2 part"
portion of the swivel couplings onto the adapter
couplings. Use a stepped spanner or a hex wrench.
Put sealing compound or Teflon tape on the threads.
Important: Hold the unit's couplings with a wrench
while tightening to avoid twisting the tubes inside
the unit.
• Fit the 3/4" female - 1/2" male adapter couplings on
the valve, then screw the "1 part" portion of the swivel
couplings onto the adapter couplings. Use sealing
compound or Teflon on the threads.
• Fit the valve on the unit at the level of the swivel
couplings. The valve is installed at the unit's water
outlet.
• Install the thermal actuator on the valve and
connect the cable in the electrical box as shown in
the electric wiring diagram.
• Mount the auxiliary tank (supplied with the unit) on the
side, below the valve. House the tank's fitting in the
hole underneath the valve. Secure the tank with the
two screws provided.
B -Valve distant from the unit's hydraulic connections
• The valve can be installed on a pipe (not supplied) enabling it to be offset from the unit's hydraulic connections.
In this case, place the valve along the unit, on the side so that it is above the auxiliary tank.
12
on
the
unit's
hydraulic
Valve
Water
Water inlet
outlet
Female
3/4" M-1/2" F
couplings of
coupling
the unit
Swivel coupling
("2 parts" portion)
Valve
Water
Water
outlet
inlet
Screw
Auxiliary tank
fitting
Screw
Swivel coupling
("1 part" portion)
3/4" M - 1/2" F adapter
couplings
Valve
Screw
Screw
Auxiliary tank fitting