IMPORTANT ADVICE REGARDING THE
INSTALLATION
Other than that described in this documentation, you are also
asked to note the following UNI standards:
- No. 10683 - rewood heat generators:
installation requirements
- No. 9615/90 - calculating the internal dimensions of replaces
- No. 10412:2 - hot water heating systems.
Speci c safety requirements for systems provi
ded with residential solid fuel burning applian
ces and combined boiler, not exceeding a total
nominal heat input of 35 kW.
Particularly:
- Before carrying out any assembly it is important to verify
compatibility of the appliance, as stipulated in UNI 10683
standard, paragraphs 4.1 / 4.1.1 / 4.1.2.
- When assembly is completed, the installer must implement
"start-up operations" and issue documentation as required
by UNI 10683 standard in paragraphs 4.6 and 5, respectively.
- The connections, commissioning and veri cation of pro-
per operation of the thermo replace must be carried out
by quali ed personnel, who can implement the electrical and
plumbing connections as required by UNI standards 10683,
paragraph 4.5 and 10412:2, apart from complying with these
assembly instructions.
- Veri cation must be carried out with the replace on and
after having been on for a couple of hours, before covering the
thermo replace, so that you can intervene if need be.
After which, the nishing operations such as:
- setting-up the replace mantel
- mounting the replace covering
- pilasters, painting, etc.
are carried out, once the tests are completed successfully.
Consequently, EDILKAMIN does not accept responsibility for
expenses deriving from demolition as well as construction even
if either occurs as a result, after having replaced any damaged
parts of the thermo replace.
EXTERNAL AIR INLET
An external connection with a 12,5 cm diameter crosssec-
tion throughout (refer to the technical table) is absolutely
necessary for the thermo replace to function properly and
is therefore imperative for this to be implemented.
This connection must link the air adjustment mechanism (E),
delivered separately. The mechanism, delivered separately,
can be assembled either right or left of the thermo repla-
ce. Connection can be made with a exible aluminium pipe.
Ensure that the points where there may be dispersion of air are
sealed well. The air adjustment mechanism (E) can be remo-
ved and mounted on the right side of the thermo replace. It is
recommended to place a protection grille on the outer part of
the air inlet channel, however, ensure that this does not reduce
the cross-section. For distances longer than 3 m or with bends,
increase the given cross-section by a minimum of 10% to a ma-
ximum of 20%. The intake of external air must enter at oor
level (it cannot enter from above).
E
INSTALLATION
CHIMNEY FLUES AND CHIMNEYPOT
The thermo replace smoke outlet has a circular crosssection
so that stainless steel pipes can be used. If the chimney ue
inlet is not vertically above the thermo replace, the connection
from the replace to the ue must not have a narrowing
section or inclinations greater than 45° ( g. 1-2-3-4).
If the chimney ue is not brand new or too big, it is recommen-
ded to t in stainless tubes of an appropriate diameter and with
suitable insulation.
If the chimney ue is installed outside, it is recommended to
use an insulated, double walled, stainless steel ue.
The characteristics of the construction must be suitable to
withstand a smoke temperature of at least 450° C, with parti-
cular reference to the mechanical resistance, insulation and the
gas tight sealing.
The junction of the steel ue inlet and the smoke outlet of the
replace must be sealed with high temperature mastic.
The fundamental characteristics of the chimneypot are:
- an internal cross-section at the base, which is the same as that
of the chimney ue.
- an outlet cross-section which is no smaller than twice that of
the chimney ue.
- its position must be high enough to catch the wind and avoid
downdraft areas in turbulent wind.
In addition to that mentioned above, please consider the
indications stipulated in UNI 10683/2005 standard, para-
graph 4.2: "connection to the smoke outlet system" and its
subsections.
max.45°
E
- 28
-
1
45°
45°
3
2
NO
4