9. 1 .2
Minimum water content
KEY
(1) Minimum water content for air
conditioning applications
(2) Minimum water content in the
case of process applications or
applications with low outside
temperatures and low load.
The pressure drops of the diagrams
are relative to the average water
temperature 10 °C. The following
table shows the correction to apply to
the pressure drop when the average
water temperature varies.
NOTE
For all models the plumbing parallel is
the responsability of the installer.
Minimum water content
1251
1401
1601
1801
2101
2401
1402
1602
1802
2002
2202
2352
2502
2652
2802
3002
3202
3402
3602
3902
4202
4502
4802
5003
5203
5403
5703
6003
6303
6603
6903
7203
5
Average water temperature °C
1,02
Multiplicative coefficient
m 3
(1)
m 3
1.9
m 3
2.2
m 3
2.4
m 3
2.9
m 3
3.3
m 3
3.7
m 3
2. 1
m 3
2.4
m 3
2.8
m 3
3.2
m 3
3.5
m 3
3.6
m 3
3.8
m 3
4.0
m 3
4.3
m 3
4.6
m 3
4.9
m 3
5.4
m 3
5.9
m 3
6.2
m 3
6.7
m 3
7.0
m 3
7.5
m 3
7.8
m 3
8.3
m 3
8.8
m 3
9. 1
m 3
9.6
m 3
9.9
m 3
10.4
m 3
10.7
m 3
11.2
10
15
20
30
1
0,985
0,97
0,95
(2)
3.9
4.4
4.9
5.9
6.5
7.5
4.3
4.8
5.6
6.3
6.9
7.3
7.6
8. 1
8.6
9.3
9.7
10.7
11.7
12.4
13.3
14.0
14.9
15.6
16.6
17.6
18.3
19.2
19.9
20.8
21.4
22.4
40
50
0,93
0,91
23