Installation instructions
A range cord rated at 40 amps with
125/250 minimum volt range is required.
A 50 amp range cord is not recommended
but if used, it should be marked for use with
nominal 1
/
" diameter connection openings.
3
8
Care should be taken to center the cable
and strain relief within the knockout hole to
keep the edge from damaging the cable.
• Because range terminals are not accessible
after range is in position, flexible service
conduit or cord must be used.
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The terminal block
will then be accessible.
Terminal block
Access cover
Specified power-supply-cord kit rating
Range rating, watts
120/240 volts
3-wire
8750 - 16500
30 English
Specified rating of
power-supply-cord kit,
120/208 volts
3-wire
7801 - 12500
NOTE
If conduit is being used, go to Step 5 on
page 32 ~ 34.
ALL NEW BRANCH-CIRCUIT
CONSTRUCTIONS, MOBILE
HOMES, RECREATIONAL
VEHICLES AND INSTALLATIONS
WHERE LOCAL CODES DO NOT ALLOW
GROUNDING THROUGH NEUTRAL, REQUIRE
A 4-CONDUCTOR UL-LISTED RANGE CORD.
amperes
Power cord
40 or 50A
Diameter (inches) of range
connection opening
Conduit
1
/
"
1
3
1
8
/
"
8