Instalación eléctrica
6
Instalación conforme a UL
Model
PZM2XA-A150-
D03-00 – When
installed with PH-
C22A-
A110M1-...A-00/..
PZM2XA-A150-
D03-00 – When
installed with PH-
C22A-
A150M1-...A-00/..
1) Drives employing Type E Combination Motor Controller model MS132-16, -25, -32 must be installed with Current Limiter Series
S803W-SCLxxx-SR manufactured by ABB, otherwise SCCR rated 30 kA/480 Vrms.
6.4.4
Motor overload protection
6.4.5
Ambient temperature
6.4.6
Wiring diagrams
58
Instrucciones de funcionamiento – MOVIPRO
Three Phase 380 V – 500 V Voltage Range
SCCR:
200 kA/500 V
When protected by:
When protected by:
Non Semiconduc-
Inverse-Time Cir-
tor Fuses (currents
are maximum va-
lues)
50 A/600 V
50 A max/500 V min
The units are provided with load and speed-sensitive overload protection and thermal
memory retention upon shutdown or power loss. The trip current is adjusted to 150 %
of the rated motor current.
The units are suitable for an ambient temperature of 40 °C, max. 60 °C with derated
output current. To determine the output current rating at temperatures higher than
40 °C, the output current should be derated 3% per °C between 40 °C and 60 °C.
NOTA
•
Use only tested units with a limited output voltage (V
output current (I
= 8 A) as an external DC 24 V voltage source.
max
•
UL certification does not apply to operation in voltage supply systems with a non-
grounded star point (IT systems).
For wiring diagrams, refer to the MOVIPRO
installation".
®
PHC2.A-A..M1-E45C-C5
SCCR:
SCCR: 65 kA/480 V
200 kA/500 V
When protected
Type E Combinationen Motor Controller
cuit Breaker
ABB, Model
MS132‑25 Ra-
ted 480 V, 15 HP
ABB, Model
MS132‑32 Ra-
ted 480 V, 20 HP
®
operating instructions, chapter "Electrical
SCCR: 65 kA/460 V
When protected by:
1)
by:
Rockwell Automa-
tion, Model
140M‑F8E-C25 Ra-
ted 460 V, 20 HP
Rockwell Automa-
tion, Model
140M‑F8E-C32 Ra-
ted 460 V, 25 HP
= DC 30 V) and limited