Jandy
Pro Series VS FloPro™ Series Variable-Speed Pump
®
ELECTRICAL SHOCK HAZARD
Due to the potential risk of fire, electric shock, or
injuries to persons, Zodiac® Pumps must be installed
in accordance with the National Electrical Code
(NEC
®
), all local electrical and safety codes, and
the occupational Safety and Health Act (OSHA).
Copies of the NEC may be ordered from the National
Protection Association, 470 Atlantic Ave., Boston,
MA 02210, or from your local government inspection
agency.
In Canada, Zodiac Pumps must be installed in
accordance with the Canadian Electrical Code (CEC).
3.
Make sure all necessary isolation valves are closed
to prevent pool water from reaching the pump.
4.
Following the markings on the locking ring, turn
the ring counter-clockwise until the 'START'
markings align with the ports. See Figures 13 and
14.
5.
Carefully remove the lid with locking ring.
Lid with
Locking
Ring
Figure 13. O-ring in Lid Assembly
WARNING
®
Seal
|
Installation & Operation Manual
Lid with
Locking
Ring
and
Seal
Pump
Debris
Trap
Basket
(Inside
Pump)
Figure 14. Exploded View of Pump
3.6
Conduct Pressure Test
When pressure testing a system with water, air
is often trapped in the system during the filling
process. This air will compress when the system is
pressurized. Should the system fail, this trapped air
can propel debris at a high speed and cause injury.
Every effort to remove trapped air must be taken,
including opening the bleed valve on the filter and
loosening the pump basket lid while filling the pump.
Trapped air in the system can cause the filter lid
to be blown off, which can result in death, serious
injury, or property damage. Be sure all air is properly
purged out of the system before operating. DO NOT
USE COMPRESSED AIR TO PRESSURE TEST OR
CHECK FOR LEAKS.
Page 15
ENGLISH
WARNING
WARNING