3. Electrical work
3.1.5. Connecting External Output
The signal in the following states can be output.
TB141
Item
1-2
(OUT1)
X1
Operation Output
3-4
(OUT2)
X2
Error Output
5-6
(OUT3)
X3
Comp. Output
7-8
(OUT4)
X4
Defrost Output
9-10
(OUT5)
X5
Mode(Cool) Output
11-12
(OUT6)
X6
Mode(Heat) Output
13-14
(OUT7)
Cable length : Maximum 50m
Output specifi cation : Non-voltage switch 1A or less , 240V AC
*Connect the surge absorber according to the load at site.
Note : External output signals are separated by basic insulation from other circuit of
interface.
Caution : When 2 or more external outputs are used, the power supply on the output
side should be the same.
3.1.6. Wiring specifi cation External output / External input
Locally supplied parts
Item
Name
External output function External output signal wire Use sheathed vinyl coated cord or cable.
Display lamp, etc.
External input function
External input signal wire
Switch
3.1.7. Switch setting
It is possible to set the following function by setting the switch of the interface controller.
• SW2-1/2-2 : Fixed operation mode
SW2-1
SW2-2
Details
OFF
OFF
Not FIX (Depending on Remote controller setting)
ON
OFF
[Cooling] FIX
OFF
ON
[Heating] FIX
ON
ON
External input (Depending on TB142-3, 4)
• SW2-3/2-4/2-5 : Fixed set temperature [For Auto mode only]
SW2-3
SW2-4
SW2-5
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
Set switches in case of auto mode.
• SW2-6 : COND./EVA. TEMP. THERMISTOR (TH5)
SW2-6
Details
Model
OFF
Effect
PAC-IF012B-E
ON
No effect
PAC-IF011B-E

3.1.8.Before test run

After completing installation and the wiring and piping of the local application and outdoor units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0MΩ.
Warning:
Do not use the system if the insulation resistance is less than 1.0MΩ.
Caution:
Do not carry out this test on the control wiring (low voltage circuit) terminals.
OFF
ON
OFF
ON
Normal
Error
OFF(Comp. OFF) ON
OFF
ON
OFF
ON
OFF
ON
X1
X2 X3 X4 X5 X6
I/F
1
2
3
4
5
6 7 8
9 10 11 12 13 14
At site
Model and specifi cations
Wire type :
CV, CVS or equivalent.
Wire size :
Stranded wire 0.5mm
Solid wire:
{0.65mm to {1.2mm
Non-voltage Contact AC220-240V (DC30V), 1A or less
Use sheathed vinyl coated cord or cable.
Wire type :
CV, CVS or equivalent.
Wire size :
Stranded wire 0.5mm
Solid wire :
{0.65mm to {1.2mm
Non-voltage "a" contact
Details
Not fi xed (Remote controller setting)
Cooling 19°C/Heating 17°C FIX
20°C FIX
22°C FIX
24°C FIX
26°C FIX
28°C FIX
Cooling 30°C/Heating 28°C FIX
(Comp. ON)
(Defrosting)
(Cooling)
(Heating)
TB141
2
to 1.25mm
2
to 1.25mm
2
2
Photo.3-6
TB141
7
Tabla de contenido
loading

Este manual también es adecuado para:

Pac-if012b-e

Tabla de contenido