Hitecsa 105 Manual De Instrucciones De Uso, Mantención E Instalación página 125

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

EN
To access the configuration parameters, insert password "48".
Menu
Par
Label
Description
label
Frost protection, mode:
On: Frost protection from "USER INTERFACE". The protection
241
AFEn
inside the PdC must be disabled (PCB DISPLAY, switch 1 on OFF)
Off: Frost protection from PdC controller (PCB DISPLAY, switch 1 to
ON)
Water temperature (par. 109 /111) below this the first level of frost
242
AFSU
protection starts up (Pump 1 on)
Outdoor air temperature (par. 108) below this the first level of frost
243
AFSA
protection starts up (Pump 1 on)
AFr
Water temperature (par. 109 /111) below this the second level of
244
AF2U
frost protection starts up (the water heats up from PcD and/or addi-
tional generator)
Frost protection, differential: The differential applied to the above
245
diFA
temperatures (AFSA,AFSU,AF2U). Exceeding this, the respective
protection levels are disabled
The water temperature, at the outlet of the heat pump, requested to
246
AFtU
trigger the second frost protection level
NOTE: If par. 110 = 3 the controls on the water temperature are not carried out on par. 111.
Enclosed documents
126
U.m.
Range
max Default t
min
-
Off
On
Off
°C
2
-10
2
°C
1
-10
1
°C
1
-15
-1
°C
1
15
5
°C
5
30
5
Correct
Address
On
16443
1644
16445
16384
16446
16447

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

110116

Tabla de contenido