Error
Description
Code
Flow tempera-
A8
ture sensor
error
PCB MAIN
C0
error
Upper fan
C1
motor error
Outdoor
C2
temperature
sensor error
Lower fan
C3
motor error
Increase in
temperature
C4
(over 110°C)
of the PCB
MAIN
PCB MAIN
C5
sensor error
PCB MAIN
C6
error
Serial error
C7
PCB
TERMINAL
BLOCK
PCB MAIN
C8
error
SMART-MT
CC
serial error
Section II :: Installation and maintenance
Relevant part Verification method
DRAIN TEMP.
Check the electrical continu-
SENSOR
ity with a tester [tables].
PCB MAIN
-------
Check the electrical continu-
FUSE CF7
ity of FUSE CF2 with a tester
[fig. 2].
FAN MOTOR
Check the voltage of the FAN
PCB MAIN
MOTOR [fig. 2].
DRAIN TEMP.
Check the electrical continu-
OUTDOOR
ity with a tester [tables].
10kW Unit: Check the electri-
cal continuity of FUSE CF6
Fuse CF7,
with a tester [fig. 1].
CF6
13-16kW Unit: Check the
electrical continuity of FUSE
CF7 with a tester [fig. 1].
FAN MOTOR
Check the voltage of the FAN
PCB MAIN
MOTOR [fig. 2].
Check the installation room
Incorrect
(air intake and output clog-
installation
ging).
DRAIN TEMP.
-------
PCB MAIN
DRAIN TEMP.
-------
PCB MAIN
PCB MAIN
-------
Incorrect PCB
MAIN - PCB
TERMINAL
Check the connection.
BLOCK con-
nection
Earth cable
-------
PCB
Fault is different from the
TERMINAL
above cases.
BLOCK
Fault is different from the
PCB MAIN
above cases.
Disconnect the power supply,
wait for about 3 minutes and
then reconnect it
PCB MAIN
Check the loosened connec-
tions and the contacts with
the reactors.
Incorrect
connections
(PCB TERMI-
Check the connections.
NAL BLOCK -
SMART-MT)
Earth cable
-------
PCB
Fault is different from the
TERMINAL
above cases.
BLOCK
Fault is different from the
SMART-MT
above cases.
Solution
Replace the sensor if it is faulty.
Replace the PCB MAIN
If fuse CF7 is blown, replace the FAN MOTOR
and the fuse. If fuse CF6 is not blown, check the
voltage of the FAN MOTOR [fig. 2]. If the voltage
is normal, replace the FAN MOTOR. If the volt-
age is abnormal, replace the PCB MAIN board.
Replace the sensor if it is faulty.
If fuse CF6 or CF7 is blown, replace the FAN
MOTOR and the fuse. If fuse CF6 or CF7 is not
blown, check the voltage FAN MOTOR and the
fuse. If the voltage is normal, replace the FAN
MOTOR. If the voltage is abnormal, replace the
PCB MAIN board.
Correct the installation position to prevent the air
intake and output pipes from clogging.
Replace the PCB MAIN
Replace the PCB MAIN.
Replace the PCB MAIN.
Once the wiring error is corrected, reactivate the
appliance.
Verify that the earth wire has been installed cor-
rectly.
Replace the PCB TERMINAL BLOCK.
Replace the PCB MAIN.
If the same error code appears again, replace the
PCB MAIN.
Check the connection of the wiring and the incor-
rect contact and then restart the appliance.
Verify that the earth wire has been installed cor-
rectly.
Replace the PCB TERMINAL BLOCK.
Replace the SMART-MT.