Description
Code
Output water
E4
temperature
sensor error
Input water
E5
temperature
sensor error
Triggered
FU
high pressure
switch
P1
Pump error
High pressure
P3
switch error
Triggered
U5
high pressure
switch
It does not cool It does not
heat
When checking the FAN MOTOR and/or the PUMP, disconnect the power supply completely before touching their terminals or
connectors.
If an open circuit is detected by the drain temperature sensor, the error is displayed 10 minutes after the appliance is acti-
vated.
If a closed circuit is detected by the drain temperature sensor, the error is displayed immediately.
Section II :: Installation and maintenance
Relevant part Verification method
DRAIN TEMP.
Check the electrical continu-
OUTPUT
ity with a tester [tables].
WATER
DRAIN TEMP.
Check the electrical continu-
INPUT
ity with a tester [tables].
WATER
Check the installation room
Output air
(air intake and output clog-
recirculation
ging).
Check the difference be-
Obstruction in
tween the water input and
the PUMP or
output. A great difference
in the hydrau-
means that the flow rate is
lic circuit
too low.
PUMP or
Check the voltage of the
PCB MAIN
PUMP [fig. 3].
PCB MAIN
Check the difference be-
Obstruction in
tween the water input and
the PUMP or
output. A great difference
in the hydrau-
means that the flow rate is
lic circuit
too low.
HIGH
Check the connection of
PRESSURE
the wiring and the incorrect
SWITCH
contact.
Check the connection of
HIGH THER-
the wiring and the incorrect
MOSTAT
contact.
OUTDOOR
Check the electrical continu-
TEMP.
ity with a tester [tables]
SENSOR
Check the service valve and
Gas leak
the cooling circuit.
4-WAY
Check the electrical continu-
ity with a tester [tables].
VALVE
Air recircula-
Check the installation room
tion (insuf-
(air intake and output clog-
ficient air
ging).
circulation)
WATER
INPUT AND
Check the electrical continu-
OUTPUT
ity with a tester [tables].
TEMP.
SENSOR
Check the service valve and
Gas leak
the cooling circuit.
Check the difference be-
Obstruction in
tween the water input and
the PUMP or
output. A great difference
in the hydrau-
means that the flow rate is
lic circuit
too low.
Solution
Replace the sensor if it is faulty.
Replace the sensor if it is faulty.
Correct the installation position to prevent the air
intake and output from clogging.
Remove the obstruction and resume operation.
If the voltage is normal, replace the PUMP. If
the voltage is abnormal, replace the PCB MAIN
board.
Remove the obstruction and resume operation.
If the same error code appears again, replace
the HIGH PRESSURE SWITCH.
If the same error code appears again, replace
the HIGH TEMPERATURE THERMOSTAT.
Replace the sensor if it is faulty
Recover the refrigerant and then reload the
required mass.
In case of an abnormal value, replace the coil.
Correct the installation position to prevent the air
intake and output from clogging.
Replace the sensor if it is faulty.
Recover the refrigerant and then reload the
required mass.
Remove the obstruction and resume operation.