"Prg" Menu parameters list 2-2
Men label Par Label Description
Frost protection mode:
- On: Frost protection by USER INTERFACE. The internal protection
241 AFEn
- Off: Frost protection from PdC controller (PCB DISPLAY switch 1
Water temperature (par. 109/111) below which there is the
242 AFSU
intervention of the first level of frost protection (Pump 1 active)
External air temperature (par. 108) under which you have the
243 AFSA
intervention of the first level of frost protection (Pump 1 active)
AFR
Water temperature (par. 109/111) below which there is the
244 AF2U
intervention of the second level of frost protection (water heating by
PdC and / or additional generator)
Frost protection, differential
245 diFA
Differential applied at temperatures above set (AFSA, AFSU, AF2U),
beyond which disables the respective levels of protection
Water temperature, the output from the heat pump, request the
246 AFtU
intervention of the second level of frost protection
HP On/Off timer profile 1, start first On period:
247
St1
Time when, for the first time, change happens from Off to On, in
profile 1
HP On/Off timer profile 1, end first On period:
248
En1
Time when, for the first time, change happens from On to Off, in
profile 1
P1
HP On/Off timer profile 1, start second On period:
249
St2
Time when, for the second time, change happens from Off to On, in
profile 1
HP On/Off timer profile 1, end second On period:
250
En2
Time when, for the second time, change happens from On to Off, in
profile 1
HP On/Off timer profile 2, start On period:
251
St
Time when change happens from Off to On, in profile 2
P2
HP On/Off timer profile 2, end On period:
252
En
Time when, for the first time, change happens from On to Off, in
profile 2
253 MOn
254
tUE
Assignment of the four profiles (P1,P2,P3,P4) to each weekday
255 UEd
1=P1 Four time bands, two On and two Off
256
tHr
dAYS
2=P2 Two time bands, one On and one Off
3=P3 Single time band always On
257
Fri
4=P4 Single time band always Off
258
SAt
259 SUn
There are also avaiables the following variables
Men label Par Label Description
-
-
-
Defrosting active or non-active (read-only)
-
-
-
On / Off unit (read / write)
-
-
-
Mode of operation Summer / Winter (reading and writing)
must be disabled to PdC (PCB DISPLAY switch 1 OFF)
ON)
Section I :: User
U. m.
min
min
min
min
min
min
U. m.
20
Range
Default KCTR
min
max
-
On
Off
Off
°C
2
-10
2
°C
2
-10
1
°C
1
-15
-1
°C
1
15
5
°C
5
30
5
h:
00:00
En1
08:00
h:
St1
St2
12:00
h:
En1
En2
14:00
h:
St2
23:59 17:00
h:
00:00
En
08:00
h:
St
23:59 17:00
-
1
4
1
-
1
4
1
-
1
4
1
-
1
4
1
-
1
4
1
-
1
4
2
-
1
4
4
Range
Default KCTR
min
max
-
-
-
-
-
-
-
-
-
-
-
-
PW
Address
S
16443
S
16444
S
16445
S
16384
S
16446
S
16447
X
16452
X
16453
X
16454
X
16455
X
16456
X
16457
X
16458
X
16459
X
16460
X
16461
X
16462
X
16463
X
16464
PW
Address
-
-
8967
-
-
16385
-
-
16387

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

110116

Tabla de contenido