Troubleshooting; Allarm Code User Interface - Hitecsa 105 Manual De Instrucciones De Uso, Mantención E Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

10.1 TROUBLESHOOTING

ATTENTION
If the unit operates incorrectly
• If the unit operates incorrectly due to a thunderstorm or amateur radio
interference, or if it stops or does not respond to the remote controller,
turn off the circuit breaker. Wait for about 3 minutes, and then turn on the
circuit breaker and press the ON/OFF button of the remote controller.
CONDITION
The unit does not start re-operation immediately.
Steaming (The Unit)
The room does not warm up or cool down.
The sound of flowing water can be heard from the floor or the radiator.
The pump is running while the unit is stopped.

10.2 ALLARM CODE USER INTERFACE

Menu Set indoor, Menu label AL
Code
Cause
AMbt
KCTR room temperature probe failure
AMbH
KCTR room humidity probe failure
OUtA
External temperature probe failure
OUtU
Outlet water temperature probe failure
"Temp. Water Supply System" signal error (terminals
3-4
3-4)
SAnt
Storage domestic hot water temperature probe failure
HP
Heat pump error. Error code on PCB display.
rEmC
Remote controller connection error
Cooling radiant system condensation risk.
The following causes are possible:
- Closed contact between the "Dew Point Sensor" IN-COM
CONd
terminals
- OUtU (Par109) < TLiM (Par229) for more than three
minutes
- InU (Par111) < TLiM (Par229) for more than three minutes
Heating radiant system overheating risk (no DHW).
The following causes are possible:
- InU (Par111) > TSUp (Par236) +2 for more than three
SUrr
minutes
- OUtU (Par109) > TReq (Par230) +2 for more than
three minutes
Section II :: Installation and maintenance
CAUTION:
Before requesting service, perform the following checks:
CAUSES OR CHECK POINTS
This is for protection of the system. After a stop, the unit does not start
operation for approx. 3 minutes.
It is caused by defrosting of the unit in heating operation.
Is the temperature set correctly on the KCTR?
Is there an open window or door?
Is there enough circulating water?
Bleed the air from the water and load
The circulation pump operates automatically at times in order to prevent
scale build-up on the pipe walls or protection antifreeze
Solution
- Check the KCTR connection
- Replace the KCTR
- Check the KCTR connection
- Check the humidity sensor connection in the KCTR
- Replace the humidity sensor
- Check the connection
- Replace the probe
- Check the connection
- Replace the probe
- Check the element connected to terminal blocks 3-4 and the setting of
parameter 300 "t3-4"
- Check the connection and setting of parameter 123 "COnt"
- Replace the probe
See alarm errors on the PCB Main Display
- Check the KCTR connection
- Replace the KCTR
- Check the hydraulic system
- Check the parameter setting
-Check the hydraulic system
- Check the parameter setting
46
EN

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

110116

Tabla de contenido