FOR 30, 50 AND 75 POUND
TUMBLERS
NATURAL GAS service must be supplied at 6-1/2 ±
1-1/2 inch water column pressure (1.62 ± .37 kPa).
L.P. GAS service must be supplied at 11 ± .3 inch water
column pressure (2.74 ± .07 kPa).
FOR 120 AND 170 POUND
TUMBLERS
NATURAL GAS service must be supplied at 7 ± 1 inch
water column pressure (1.74 ± .23 kPa).
L.P. GAS service must be supplied at 11 ± .3 inch water
column pressure (2.74 ± .07 kPa).
Pressure checks can be made at the shut-off valve, see
Figure 6.
Purge air and sediment from the gas service line before
connecting it loosely to the tumbler. Purge remaining air
until odor of gas is detected, then tighten connection. Use
pipe compound, resistant to actions of L.P. gas, on all
pipe threads.
M414670
© Published by permission of the copyright owner – DO NOT COPY or TRANSMIT
WARNING
Check all pipe connections, internal and
external, for gas leaks using a soapy
solution. To reduce the risk of explosion or
fire, DO NOT USE AN OPEN FLAME TO
CHECK FOR GAS LEAKS! Gas
connections should be checked annually
for leakage.
GAS LINE
TO
DRYER
CONTROLS
SHUT-OFF
VALVE
DIRT AND
WATER VAPOR
1/8" (.32 cm) N.P.T. plugged
tapping accessible for
pressure testing. Gauge
connection located upstream
from dryer main manual
shut-off
Figure 6
GAS SUPPLY
PIPING SYSTEM
GAS
"T" FITTING
6 INCHES (15.2 cm)
MINIMUM GAS PIPE
TRAP
GAS
PIPE CAP
T135IE1A
W063
31