8.1 Power board fuse replacement

Proceed as indicated below (reserved for qualified technical
personnel only):
• Disconnect the power to the equipment.
• Remove the top cover of the equipment and then the power
board cover.
• Remove the fuse cap, then the fuse, using a suitable screw-
driver.
• Install a new IEC-60127-2/II certified time-delay 5 A fuse,
then refit the protective cap.
• Reassemble all the plastics and make sure the equipment is
correctly installed before powering it.

8.2 Heating element safety thermostat reset

This equipment has a manual-reset safety thermostat connect-
ed in series with the heating element immersed in water, which
interrupts the power supply in case of overtemperature inside
the tank.
If necessary, proceed as follows to reset the thermostat (re-
served for qualified technical personnel):
• Unplug the product.
• Remove any air ducts.
• Remove the top cover by first undoing the locking screws
(fig. 41).
• Remove the front panel and manually reset the tripped safety
thermostat (fig. 42). In case of intervention, the central pin of
94
EN
fig. 40
cod. 3541T630 - Rev. 03 - 05/2020
DORA
the thermostat comes out by about 2 mm.
• Refit the previously removed top cover.
fig. 41 - Top cover removal
fig. 42 - Front panel removal
200 HT - 260 HT