DOUBLE
To avoid draught problems, each stove should have
the others should be situated at a distance of at least 2
metres and the stove's chimney top should be at least 40
cm ABOVE the others (Fig. 6.4). If the chimney tops are
near each other install some dividing panels.
Fig. 6.6 (FLAT ROOF; B service compartment) and
Fig. 6.7 (SLOPING ROOF; B above the ridge) show
suggestions on the minimum distances and chimney
top positions.
been used it should be cleaned thoroughly to avoid
malfunctions and the danger of unburned parts deposited
should be cleaned at least once a year except for different
regulations.
cod. 004771651 MBL - 10/2015 - Palazzetti - PN - Italy
INSTALLATION
.
C
ONSIGLI
C
OMIGNOLI
Chimney tops, distances and positioning;Schornsteine, Abstände und Positionierung
Inclinazione del tetto
Roof slant
Neigung des Dachs
> 5 m
> A
≤ A
α
:
Recommendations - Beratung
,
DISTANZE E POSIZIONAMENTO
Distanza colmo-camino
Distance ridge cap-chimney
A[m]
< 1,85
15°
> 1,85
< 1,5
30°
> 1,5
< 1,3
45°
> 1,3
< 1,2
60°
> 1,2
- 6.5 -
≤ 5 m
B
- 6.6 -
H min
0,50 m
- 6.7 -
altezza min del camino (dallo
sbocco)
minimum chimney height
Mindesthöhe des Kamins
H[m]
0,5 oltre il colmo; above the ridge of
1 dal tetto; from the roof; vom Dach
0,5 oltre il colmo; above the ridge of
1,3 dal tetto; from the roof; vom
Dach
0,5 oltre il colmo; above the ridge of
2 dal tetto; from the roof ; vom
Dach
0,5 oltre il colmo; above the ridge of
2,6 dal tetto; from the roof; vom
Dach