6. Electrical work
If the indoor and outdoor units have separate power supplies, refer to the table at the
below. If the optional wiring replacement kit is used, change the indoor unit electrical
box wiring refering to the figure in the right and the DIP switch settings of the outdoor
unit control board.
Indoor power supply terminal kit (option)
Indoor unit electrical box connector con-
nection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Indoor unit L-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 120 m
For PUHZ-RP100/125/140 YHA application, use shield wires. The shield part must be grounded with the indoor unit OR the outdoor unit, NOT with both.
*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer than other cables.
B
A
30
30
46
C
Fig. 6-2
(2)
D
C
A
E
F
I
G
H
Fig. 6-3
H
(3)
J
Fig. 6-4
8
Indoor unit specifications
Required
Required
Required
ON
3
(SW8)
OFF
1
2
*1
*2
*3
*4
*4
*4
*4
A Remote controller profile
B Required clearances surrounding the
remote controller
C Installation pitch
B
B-1.
B-2.
H
I
I
C Wall
D Conduit
E Lock nut
F Bushing
G Switch box
H Remote controller cord
I Seal with putty
J Wood screw
Connectors (connections when shipped
Electric heater
from the factory are for indoor unit power
(For models with
supplied from outdoor unit)
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
PCA
~/N (single), 50 Hz, 230 V
16 A
2 × Min. 1.5
1 × Min. 1.5
2 × Min. 0.3
–
2 × 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
(mm)
6.2. Remote controller (Fig. 6-2)
For wired remote controller
1) Installing procedures
(1) Select an installing position for the remote controller.
The temperature sensors are located on both remote controller and indoor unit.
s Procure the following parts locally:
Two piece switch box
Thin copper conduit tube
Lock nuts and bushings
(2) Seal the service entrance for the remote controller cord with putty to prevent pos-
sible invasion of dew drops, water, cockroaches or worms. (Fig.6-3)
A For installation in the switch box:
B For direct installation on the wall select one of the following:
• Prepare a hole through the wall to pass the remote controller cord (in order to run
the remote controller cord from the back), then seal the hole with putty.
• Run the remote controller cord through the cut-out upper case, then seal the cut-
out notch with putty similarly as above.
B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:
(3) For direct installation on the wall (Fig.6-4)
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
ORANGE
figure.
CND
Indoor unit
Electric heater
control board
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
Connectors
ORANGE
CND
Indoor unit
control board