6.2 Dry heat
6.3 Change of temperature
6.4 Damp heat
7. Mechanical requirements
7.1. Vibration
7.2. Shock
7.3. Bump
7.4. Seismic
8. Electrical environmental
requirements
8.1. CT Entrada continuous
overload
8.2. CT Entrada short time
overload
8.3. VT Entrada continuous
overload
8.4. VT Entrada short time
overload
9. Enclosure protection
Quality Management System
www.fanox.com
IEC 60068-2-2
Dry Heat Operation Bb, +70ºC, 72h
Dry Heat transport & Storage Bd, +85ºC, 72h
IEC 60068-2-14
Change of Temperature Nb, Upper temp
+70ºC, Lower temp -25ºC, 5 cycles, Exposure
time 3h, Transfer time 2 min.
IEC 60068-2-30
Damp Heat Cyclic Db, Upper temp +40ºC,
Humidity 93%, 2 cycles. Relay energized
IEC 60068-2-78
Damp Heat Steady State Test Cab, Upper
temp +40ºC, Humidity 85%, 2 days. Relay not
energized
IEC 60255-27
IEC 60255-21-1
Vibration response, Class 1, 10Hz to 59Hz,
0,035mm and 59Hz to 150Hz, 0.5g
IEC 60068-2-6
endurance, Class 1, 10Hz to 150Hz, 1g
Shock Response, Class 1, 5g
IEC 60255-21-2
Withstands, Class 1, 15g
IEC 60068-21-2
IEC 60255-21-2
Bump, Class 1, 10g
IEC 60068-21-2
IEC 60255-21-3
Single Axis Sine Sweep, Class 1, X Axis: 1 to
9Hz, 3.5mm and 9 to 35Hz, 1g
IEC 60068-21-3
9Hz, 1.5mm and 9 to 35Hz, 0.5g
IEC 60255-27
3xIn without damage for continuous operation
IEC 60255-27
70xIn without damage for 1s short time
overloading
IEC 60255-27
Declared on manual, without damage for
continuous operation
IEC 60255-27
Declared on manual, without damage for 10s
short time overloading
IEC 60255-27
IP-54
IEC 60529
ISO 9001:2008
Rev.05