1.13. Pulse magnetic fields
1.14. Damped oscillatory
magnetic fields
1.15. Ring wave immunity test
2. Product safety requirements
(including thermal short time
rating)
2.1. Impulse voltage
2.2. AC or DC dielectric voltage
2.3. Insulation resistance
2.4. Protective bonding
resistance
3. Burden
3.1. AC burden for CT
3.2. AC burden for VT
3.3. AC, DC burden for power
supply
3.4. AC, DC burden for binary
Entradas
4. Contact performance
5. Communication
requirements
6. Climatic environmental
requirements
6.1. Cold
www.fanox.com
IEC 61000-4-9
Field strenght 1000 A/m, Cadence between
pulses 40s.
IEC 61000-4-10
Level 5, Field strenght 100 A/m, Frecuencia
100KHz and 1MHz, Repetition Frecuencia 40
trans./s at 100KHz, 400 trans/s at 1MHz,
Duration of each application 3s.
IEC 61000-4-12
Level 4, Line to earth for all terminals ±4kV.
Line to Line for all terminals excepts
Communication port ±2kV
IEC 60255-27
Each group to earth and with rest of the groups
in short-circuit ±5kV. Differential mode for each
IEC 60255-5
one of the groups ±1kV
IEC 60255-27
Each group to earth and with rest of the groups
in short-circuit 2kVac, 50Hz, 1 minute
IEC 60255-5
IEC 60255-27
500V applied between each group to earth and
with rest of the groups in short-circuit
IEC 60255-5
IEC 60255-27
Test current 2xIn, Test voltage 12Vac during
60s. Resistance shall be less than 0.1 ohm
IEC 60255-1
Declared on manual
IEC 60255-27
ModBus RTU
IEC 61850
IEC 60870-5-103
IEC 60870-5-104
DNP 3.0
IEC 60255-27
IEC 60068-2-1
Cold Operation Ab, -25ºC, 72h
Cold transport & Storage Ad, -40ºC, 72h