PARAMETER
VALUE
SEn1
0.0A - 14.0A
SEn2
0.0A - 14.0A
rAAP
0 - 100
rACh
0 - 100
t.CvE
0.0" - 3.0"
St.AP
PAUS
ChiU
no
St.Ch
StoP
APEr
St.PA
ChiU
no
PAUS
DESCRIPTION
Enable the obstacle sensor for motor 1
This menu allows you to regulate the sensitivity of the obstacle sensor for
motor 1. When the current absorbed by the motor exceeds the set value,
the controller detects an alarm.
When the sensor intervenes, the gate stops and is operated in the reverse
direction for 3 seconds to remove the obstacle.
The next start command restarts the movement in the previous direction.
m
0.0A
If set to
, this function is disabled
m
WARNING: if either the limit switches or the slowing down
are disabled, when detected an obstacle the control unit stops the
opening or closing phase without inverting the motion.
Enable the obstacle sensor for motor 2
Slow down in opening
This menu allows regulating the percentage of the ride/drive that is carried
out at reduced speed during the last opening stretch
Slow down in closing
This menu allows regulating the percentage of the ride/drive that is carried
out at reduced speed during the last closing stretch
Fast closing time after slowing down
If a slowing time other than 0 is set up, it could be likely that the gate
speed is not enough for the lock to fasten during the closing phase.
In case this function is enabled, once the slowing down phase is finished,
the control unit will give a normal speed command (that is to say, with no
slowing down) for the set up time.
m
WARNING: in case the gate has no electric lock,
0
set the value
.
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the opening phase
The gate stops and goes to pause
The gate immediately starts closing
The gate go on with the opening phase (command is ignored)
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the closing phase
The gate stops and its cycle is considered as finished
The gate opens again
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a Start
command when the gate is open during its pause phase
The gate starts closing
Command is ignored
Ch.AU
The pause time is reset (
)
- 39 -
DEFAULT
MEMO
0.0A
0.0A
0
0
0.0"
PAUS
StoP
ChiU