4.3
Calibration menu
To enter the calibration menu, press the ▼ key for more than one second but
less than three seconds. The display shows a flashing point on the bottom right
indicating the calibration mode.
4.3.1
ZE – Calibrate the zero-point
1. Navigate using the ▲ or ▼ keys until the display shows ZE ("ZEro") and
confirm by pressing the (▲+▼) keys. The output signal switches to 3.4 mA.
The display shows the currently measured gas concentration (negative
values are displayed up to "–5" or "–,9").
2. Apply zero gas to the sensor and wait for signal stabilisation (max.
3 minutes).
3. Press the ( +▼) keys to save the displayed value as a new zero-point.
4. Press the (▲+▼) keys once again to exit the function. The ZE display
appears once again.
5. Press the ▼ key to the calibrate the sensitivity or
6. Press the
button to switch back to the measuring mode.
4.3.2
SP – Calibrate the sensitivity
1. Navigate using the ▲ or ▼ keys until the display shows SP ("SPan") and
confirm by pressing the (▲+▼) keys.
|
The display shows the test gas concentration used during the previous
adjustment in % LEL.
Use the ▲ or ▼ key to set the concentration of the test gas currently in
use between 20 and 99% LEL in 1% LEL steps (or 0.1% LEL steps
between 2.0 and 9.9% LEL). Pressing the keys for a longer period
activates the repeat function.
2. Press the (▲+▼) keys, apply test gas to the sensor and wait until the
displayed measured value has stabilised (maximum of 3 minutes).
3. Press the (▲+▼) keys to recalculate and save the internal amplification.
4. Press the (▲+▼) keys to display a reference value for the sensor's
sensitivity (constantly amplified bridge signal).
5. Press the (▲+▼) keys to exit the function. The display shows SP once
again.
6. Press the ▲ key twice to return to measuring mode.
4.4
Maintenance menu
To enter the maintenance menu, press the ▼ key for more than 3 seconds until
the display shows "SL" and the point in the bottom right corner flashes to
indicate the maintenance state.
4.4.1
SL – set current output to X mA
This function can be used to set the transmitter's output signals to specific
constant values for test purposes.
This function can trigger alarms at the controller!
1. Navigate using the ▲ or ▼ keys until the display shows SL ("Set Loop") and
confirm by pressing the (▲+▼) keys.
The current output of the transmitter is set to 4 mA, the display shows
"04".
|
en
Control
25