only with
0 / 4 ... 20 mA
GND
Inductive load
GND
Fig. 5: Electrical connection with 7-pin M16 plug
7 Commissioning
7.1 Notes on safety
Danger to life due to dangerous operating states when using serial commu-
nication
If the interface is used, interference from radio waves or other electrical inter-
ference can trigger a reaction. The product no longer responds to the defined
set point.
Make sure that no interference is present when using the interface.
u
7.2 Basic requirements
Product-specific requirements
• In case of supply pressure interruption: Switch off 24 V supply voltage (mate-
rial protection).
• Only operate the product with a voltage source and control voltage suitable
for PELV. The voltage source must ensure secure electrical isolation of the op-
erating voltage from the mains in accordance with IEC / EN 60204-1 (accident
prevention).
• The communication interface is only intended for maintenance and parame-
terization and not for continuous operation. Take precautions against uncon-
trolled movement of system parts (accident prevention, material protection).
• Before opening the sealing cap, make sure that the environment is free from
humidity and dust.
AVENTICS™ Sentronic 625 | IM502079-014-R01 | English
Control
+24 V DC (supply voltage)
0 V DC (supply voltage)
GND
Analog input (set point)
0 ... 10 V
(or 0 / 4 ... 20 mA)
10 V
Set point mass
Not connected
Analog output (actual value)
max.
0 ... 10 V
500 Ω
(or 0 / 4 ... 20 mA)
Set point mass
Digital output
(pressure switch)
max. 200 mA / 4.8 W
Shield
FE
DANGER
M16 plug, 7-pin.
M16 electrical
connector of the cable
1
2
3
4
5
6
7
Shield
Housing M16 electrical
connector
• IP protection and EMC protection are only ensured if the sealing cap of the
communication interface is closed properly. Remove the parameterization
adapter during normal operation and close the housing properly with the seal-
ing cap.
7.3 Preparation
7.4 Step-by-step commissioning
Procedure
1. Switch on the pneumatic supply.
2. Screw in the sealing cap to the stop.
3. Switch on the 24 V DC supply voltage.
4. Set the pressure.
4
M16 flange plug of the
valve
3
250 Ω with
set point 0 / 4 ... 20 mA
Housing M16 flange plug
M4 connection valve housing
See g 8.4 Manual pressure adjustment (manual
5
6
7
1
2
mode).
22