SETTING PARAMETERS USING THE REMOTE CONTROL
Turn knob B
Press knob B
Press button A or C
KEY TO FIGURE MENU
1
Enduser
2
Commissioning
ALL MODIFIED PARAMETERS SHOULD BE NOTED
DOWN IN THE TABLE AT THE END OF THIS MANUAL.
The following procedure is used to access the four boiler pro-
gramming menus:
• from the main menu
•
A and C (hold down for approx. 6 seconds)
B
menu 1-2-3-4 (see figure to side and key).
•
C to go back one menu at a time to the main menu.
When the Control Panel is wall-mounted enable the room sen-
sor and flow temperature modulation as follows:
A) ROOM SENSOR
• Access menu 2.
•
B
Operator unit
•
B
programme row 40 (Used as)
•
B (anti-clockwise)
For correct operation of the environment unit during the reduced time band it is necessary to set the parameter 5977 = "none".
B) FLOW TEMPERATURE MODULATION
To set flow temperature modulation, disable parameter 742 (HC1). Proceed as follows:
• Access menu 2.
•
B
Temps / mode CH1
B (anti-clockwise)
•
If, when turning the knob B on the main menu, the display visualises the boiler flow temperature instead of the ambient tem-
perature, parameter 742 has not been set correctly.
After every system configuration (e.g.: solar combination, connection an external storage boiler, etc.) perform the following proce-
dure to update the boiler board to the new configuration:
• Access menu 2 as indicated at the beginning of this section.
•
B
Configuration
•
B
Yes then
B to confirm.
ZONE SYSTEM WITH INSTALLATION OF THE REMOTE CONTROL
The electrical connection and the adjustments required to manage a system divided into zones with use of the Remote Control
differs according on the accessories connected to the boiler. To install and configure, see the instructions of the Expansion Mo-
dule supplied as an accessory.
ADJUSTING THE TEMPERATURE OF THE HIGH TEMPERATURE HEATING SYSTEM
To avoid frequent starting and stopping, raise the minimum temperature setpoint of the boiler in the heating mode by setting pa-
rameters 740, to not less than 45°C, using the procedure described in point B.
TEMPERATURE ADJUSTMENT ON LOW TEMPERATURE HEATING SYSTEM
For a low temperature system (such as underfloor heating), reduce the maximum CH temperature setpoint on the boiler by setting
parameter 741 (point B) to a value not greater than 45°C.
7104645.02 (1-01/12)
SYMBOLS FOR REMOTE CONTROL
3
Engineer
4
OEM
C.
B to confirm.
B.
Room unit 1
B to confirm (the room sensor is now active).
B to confirm
B to confirm.
"---" then
B
B
programme row 6200 then
Display shows
Press button A and knob B together
Press buttons A and C together
B
742 (Flow temp setpoint room stat)
B.
30
B to confirm.