Correction Set (CSt):
SF1
SF2
SF1: user set (U06);
SF2: user set (U08);
TF1: user set (U07);
TF2: user set (U09);
In both heating and cooling mode, the working set is automatically calculated based on the outside temperature according to the logic shown in the diagrams.
6
INSTALLER MENU
N.
Code
N00
Reg
Input/output
N01
oFF
Cooling force off (°C)
N02
oFC
Heating force off (°C)
N03
SAF
Force off resetting band. (°C)
N04
int
Integral (sec)
N05
AG
Anti-freeze (°C)
N06
FrP
Anti-freeze protection
N07
Rin
Supplementary heater
TF1
TF2
Name
Min
Default
0
0
-30.0
4.0
-30.0
64.0
0.0
10.0
0
600
-30.0
3.0
0
2
0
0
SF1
SF2
TF1
SC1: user set (U10);
SC2: user set (U12);
TC1: user set (U11);
TC2: user set (U13);
Max
If 0 - the machine makes adjustments in relation to the output temperature. If 1 - it
makes adjustments in relation to the input temperature. If 2 - the machine makes
adjustments in relation to the temperature of the remote probe ready by the DHW
2
control panel (if the remote probe is faulty, the machine resumes adjustments
through the input probe. if domestic hot water production is activated, the
adjustment is automatically forced on the water output temperature regardless of
the value of this parameter.
Force off limit on which to run the machine for cooling (once this limit is reached,
the compressor shuts down but no alarms are signalled). This threshold is only
70.0
active if the low water content algorithm is used. It is always active on the water
outlet even if inlet regulation is selected.
Force off limit on which to run the machine for heating (once this limit is reached,
the compressor shuts down but no alarms are signalled). This threshold is only
145.0
active if the low water content algorithm is used. It is always active on the water
outlet even if inlet regulation is selected.
Maximum safety band used to calculate the compressor reset temperature after a
20.0
force off situation.
Integral parameter. It shows the time interval in which a proportional error
999
equivalent to 1°C is such to cause the thermostat to be activated.
70.0
Anti-freeze alarm threshold
0: Antifreeze heater operating in standby without pump activated;
1: Antifreeze heater installed and operating even in standby by pump is switched
2
on;
2: With an external air temperature of < 3° the pump is activated for 2' every 30' to
monitor the water temperature throughout the entire system.
Supplementary heater presence:
0: no supplementary heater;
1: Supplementary heater fitted but not activated during domestic hot water
production;
4
2: Heater activation command used as enable for starting external boiler;
3: Supplementary heater fitted and activated during domestic hot water
production;
4: electric heater activation command used as consent for activation of an external
boiler also in a supplementary mode.