Make sure that the installation location meets the following conditions:
-
The area is completely water proof.
-
The floor is flat and level.
-
There are no flammable or explosive materials.
-
The ambient temperature is within the range from 0°C to 50°C.
-
The temperature and humidity is maintained at a constant level.
-
There is minimal dust and dirt in the area.
-
The distance from a heat source greater than 2 meters.
-
The distance from air outlet of inverter is more than 0.5 meters.
-
The installation area shall avoid of direct sunlight.
-
There is no mandatory ventilation requirements for battery module, but please
avoid of installation in confined area. The aeration shall avoid of high salinity,
humidity or temperature.
CAUTION: If the ambient temperature is outside the operating range, the battery
pack stops operating to protect itself. The optimal temperature range for the
battery pack to operate is 0°C to 50°C. Frequent exposure to harsh temperatures
may deteriorate the performance and life of the battery pack.
GROUNDING:
The ground wires must be cables green-yellow
of 10 AWG or more. After connection, the
resistance from the point of ground connection
of the battery to the connection to the ground
rod must be less than 0.1 Ω.1.
Install a ground cable in communication with all
modules. Use a separate rod.
To connect the ground line to the batteries
just drill a hole in the frame of each battery and
connect with a screw.
NOTE: be sure to drill in a safe place (as
showed in photo to cannot internally damage
the battery.
Sand around the hole well to ensure that
the paint does not limit a correct conductivity.
Do not connect the inverter to this ground line.
The inverter already has its own ground
connection to through AC power.