Error code
Description
F46
backup battery fault
AC over frequency
F47
AC lower frequency
F48
F55
DC busbar voltage is too high
F56
DC busbar voltage is too low
F58
BMS communication fault
F62
DRMs0_stop
F63
ARC fault
Heat sink high
F64
temperaturefailure
1,Please check each battery status, such as voltage/ SOC and
parameters etc., and make sure all the parameters are same.
2,If the fault still exists, please contact us for help
Grid frequency out of range
1. Check the frequency is in the range of specification or not;
2. Check whether AC cables are firmly and correctly connected;
3. Seek help from us, if can not go back to normal state.
Grid frequency out of range
1. Check the frequency is in the range of specification or not;
2. Check whether AC cables are firmly and correctly connected;
3. Seek help from us, if can not go back to normal state.
BUS voltage is too high
1. Check whether battery voltage is too high;
2. check the PV input voltage, make sure it is within the allowed
range;
3. Seek help from us, if can not go back to normal state.
Battery voltage low
1. Check whether battery voltage is too low;
2. If the battery voltage is too low, using PV or grid to
charge thebattery;
3. Seek help from us, if can not go back to normal state.
1, it tells the communication between hybrid inverter and battery
BMS disconnected when "BMS_Err-Stop" is active"
2, if don't want to see this happen, you can disable
"BMS_Err-Stop" item on the LCD.
3, If the fault still exists, please contact us for help
1, the DRM function is for Australia market only.
2, Check the DRM function is active or not
3, Seek help from us, if can not go back to normal state after
restart the system
1. ARC fault detection is only for US market;
2. Check PV module cable connection and clear the fault;
3. Seek help from us, if can not go back to normal state
Heat sink temperature is too high
1. Check whether the work environment temperature is too high;
2. Turn off the inverter for 10mins and restart;
3. Seek help from us, if can not go back to normal state.
Chart 7-1 Fault informa�on
- 42-
Solutions