V-TAC SUN-5K-SG04LP3-EU Manual De Instrucciones página 36

Idiomas disponibles

Idiomas disponibles

Time Of Use
Time
5:00
9:00
13:00
17:00
17:00
21:00
21:00
01:00
Battery Setting
Start
30%
A
40A
Grid Charge
Gen Charge
Gen Signal
Grid Signal
Gen Max Run Time
0.0 hours
Gen Down Time
0.5 hours
Time Of Use
Time
5:00
8:00
10:00
15:00
15:00
18:00
18:00
01:00
Mon
Tue
Wed
Thu
Fri
Power
Batt
Work
12000
49.0V
Mode2
12000
50.2V
12000
50.9V
12000
51.4V
12000
47.1V
49.0V
12000
30%
Batt
40A
Set2
Power
Batt
Work
12000
80%
Mode2
12000
40%
12000
40%
12000
80%
12000
40%
12000
35%
Sat
Sun
Work
Mode4
Time of use: it is used to program when to use grid or
generator to charge the ba�ery, and when to discharge
the ba�ery to power the load. Only �ck "Time Of Use"
then the follow items (Grid, charge, �me, power etc.)
will take effect.
Note: when in selling first mode and click �me of use,
the ba�ery power can be sold into grid.
Grid charge: u�lize grid to charge the ba�ery in a �me
period.
Gen charge: u�lize diesel generator to charge the ba�ery
in a �me period.
Time: real �me, range of 01:00-24:00.
Note: when the grid is present, only the "�me of use"
is �cked, then the ba�ery will discharge. Otherwise,
the ba�ery won't discharge even the ba�ery SOC is
full. But in the off-grid mode (when grid is not
available, inverter will work in the off-grid mode
automa�cally).
Power: Max. discharge power of ba�ery allowed.
Ba�(V or SOC %): ba�ery SOC % or voltage at when the
ac�on is to happen.
For example
During 01:00-05:00,
if ba�ery SOC is lower than 80%, it will use grid to charge the
ba�ery un�l ba�ery SOC reaches 80%.
During 05:00-08:00,
if ba�ery SOC is higher than 40%, hybrid inverter will discharge
the ba�ery un�l the SOC reaches 40%. At the same �me,
if ba�ery SOC is lower than 40%, then grid will charge the
ba�ery SOC to 40%.
During 08:00-10:00,
if ba�ery SOC is higher than 40%, hybrid inverter will discharge
the ba�ery un�l the SOC reaches 40%.
During 10:00-15:00,
when ba�ery SOC is higher than 80%, hybrid inverter will
discharge the ba�ery un�l the SOC reaches 80%.
During 15:00-18:00,
when ba�ery SOC is higher than 40%, hybrid inverter will discharge
the ba�ery un�l the SOC reaches 40%.
During 18:00-01:00,
when ba�ery SOC is higher than 35%, hybrid inverter will discharge
the ba�ery un�l the SOC reaches 35%.
It allows users to choose which day to execute the
se�ng of "Time of Use".
For example, the inverter will execute the �me of use
page on Mon/Tue/Wed/Thu/Fri/Sat only.
- 34 -