IT-GB-FR-ES mod. 502-502X-502L-502LX
- Empty the burner basket from the fuel and put it again in its
correct place.
- Push P4 and keep it pushed for few seconds until the
display reports the start of the lighting
.
STARTING OF NORMAL CYCLE
- Push P4 and keep it pushed for few seconds
The appliance begins an automatic cycle to effect the lighting, this cycle is composed by 3
phases, which are shown on the display :
1- START (duration approx. 2 min.)
2-LOAD PELLET (max. duration 18/20 min)
(lighting element starts heating)
(fuel loading)
FLAME LIGHT
When the starting cycle is finished the appliance
3-
(Burner stabilisation)
will function on set power level.
The appliance controls continuously the room temperature, in
case that the set power would be sufficient to exceed the
selected values, the equipment will reduce automatically the
power to minimum to avoid waste of combustible. In case that
the equipment will reduce automatically the power (modulation)
the display signal
"WORK MODULAT-"
EQUIPMENT SWITCH OFF
-Pushing for few seconds the P4 on the
control panel, the appliance starts the
switching off phase. The screw feeder motor will be disconnected and the pellet stops falling
down. The two fan ( the one of gas combustion and the one of convection) will continue to
work for some minutes until the exhaust gas temperature has sufficiently been reduced, then
the fans will automatically stop.
47/120