Installer menu [SERVICE]
ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAM-
ETERS.
Access the Main menu [MENU] with the button
Follow the path installer menu [Service] >enter the Password 1234 (see fig. 17). Confirm with
the button
.
Parameter modification menu [TSP]
Press the heating buttons to scroll the list, press the button
press the DHW, buttons, confirm with the button
Table 10- Transparent Parameters Table
Index
Description
b01
Boiler type selection
b02
Boiler type
b03
Gas type
b04
System water pressure protection selection
b05
Summer/Winter mode
b06
Variable input contact operation selection
b07
Relay card LC32 operation selection
b08
Not implemented
b09
Fault 20 status selection
b10
Not implemented
b11
Hot water tank preparation
b12
Hot water tank priority
b13
Heating priority
b14
DHW factor (not used)
b15
Not implemented
b16
Not implemented
b17
Not implemented
b18
DHW mode activation flow rate
b19
DHW mode deactivation flow rate (not used)
b20
Flue material selection
b21
Not implemented
b22
Not implemented
b23
Standard flue shutdown maximum temperature
b24
PVC flue shutdown maximum temperature
b25
CPVC flue shutdown maximum temperature
b26
Not implemented
316
BlueHelix HiTech RRT H
.
or cancel with the button
Range
2 = HEATING ONLY (also with OPTIONAL HOT
WATER TANK)
1 = 18 kW
2 = 28 kW
3 = 34 kW
4 = 45 kW
5 = Hybrid 24 H
6 = Hybrid 28 C
7 = Hybrid 34 C
0 = Natural gas
1 = Liquefied gas
2 = Propane-air
0 = Pressure switch
1 = Pressure transducer
0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0 = Flowmeter exclusion
1 = System thermostat
2 = Second room therm.
3 = Warning/Alert
4 = Safety thermostat
0 = External gas valve
1 = Alarm
2 = System filling solenoid valve
3 = Legionella pump
4 = Second heating pump
5 = Alarm2
6 = Burner lit
7 = Frost protection On
--
0 = Deactivated
1 = Enabled (only for versions with pressure trans-
ducer)
--
0 = Fixed primary (P44)
1 = Linked to DHW Setpoint (P51)
0 ÷ 255 min
0 ÷ 255 min
0 - 1
--
--
--
0 ÷ 100l/min/10 (do not set this value below 16)
0-100 l/min/10
0 = Standard
1 = PVC
2 = CPVC
--
--
60-110°C
60-110°C
60-110°C
--
cod. 3541V484 - Rev 02 - 01/2024
to display the value. To modify,
.
Default
2
1 = 18 kW
2 = 28 kW
3 = 34 kW
4 = 45 kW
5 = Hybrid 24 H
6 = Hybrid 28 C
7 = Hybrid 34 C
0
1
0 = Enabled
2
0
24
0
--
0
30
15
0
3
--
--
25
20
0
--
--
105
93
98
--