Mitsubishi Electric Mr.SLIM PUZ-A-NHA3 Manual De Instalación página 7

Ocultar thumbs Ver también para Mr.SLIM PUZ-A-NHA3:
Idiomas disponibles

Idiomas disponibles

4. Installing the refrigerant piping
A24, A36 : A+B+C 350m, 165 ft
Fig. 4-8
5. Drainage piping work
| B-C |S 8m, 26 ft
4.7. For twin combination (For A24, A36 only)
Refrigerant piping limitation of length, height difference are shown in the figure. (Fig.
4-8)
® Indoor unit
Outdoor unit
© Multi distribution pipe (option)
® Height difference (Indoor unit-Outdoor unit) Max. 30 m, 100 ft
® Height difference (Indoor unit-Indoor unit) Max. 1m, 3 ft
Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
A12, A18
|
A24-A42
Drain socket
PAC-SG61DS-E
Drain pan
PAC-SG63DP-E
|
PAC-SG64DP-E
6. Electrical work
6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)
m A12, A18
@® Remove the service panel.
® Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.
® indoor unit
Outdoor unit
© Remote controller
© Main switch (Breaker)
® Earth
® Earth terminal
Terminal block
© Clamp
© Service panel
® Wire the cables so that they do not
contact the center of the service
panel or the gas valve.
Fig. 6-2
loading

Este manual también es adecuado para:

Mr.slim puz-a-nha3-bsMr.slim puy-a:-nha3Mr.slim puy-a:nha3-bs