Tuthill FILL-RITE 900CD Manual De Instalación, Operación Y Seguridad Del Propietario página 7

Medidor digital de líquido
Idiomas disponibles

Idiomas disponibles

Further troubleshooting information can be found in your pump manual. If you need
additional assistance, please contact us at 1-800-634-2695 (M-F 8 AM–5 PM ET).
Concern
Counter inaccurate.
Low flow capacity.
Meter body cracks.
Nutating Disc Broken.
Fluid Compatibility
The 900DB series meter IS compatible with the following fluids:
Diesel Fuel
Bio-Diesel (up to B20) Mineral Spirits Heptane Hexane Gasoline, E15
The 900DB series meter IS NOT compatible with the following fluids:
Bleach Hydrochloric Acid Ink Sulfuric Acid Salt Water
CAUTION! If in doubt about compatibility of a specific fluid, contact supplier of
fluid to check for any adverse reactions to the following wetted materials:
Aluminum Stainless Steel Fluorocarbon Buna N Polyester Nickel Acetal
Assembly and Disassembly
The 900 Series Digital Meter consists of a chamber housing, measuring chamber, drive
shaft, digital counter assembly, and cover. The design of the meter is such that it can be
completely disassembled without disturbing the piping (refer to diagram on page 9 for item
number parts).
Accessing the Battery
For access to the batteries (2 AA batteries) (figure 1):
1)
Remove the four screws at the top and bottom of the front
bezel (Torx #T25).
2)
Lift bezel off. Batteries
are located on the back
side of the display; use a
Phillips head screwdriver
to remove the cover
screws to access the
batteries.
3)
Reassemble by
reversing this procedure.
Possible Cause
Meter mis-calibrated.
Air in lines or metering
chamber.
Measuring disc is
sticking.
Clogged meter
chamber.
Excess line pressure.
Sudden high pressure
fluid hitting disc.
7
Recommended Repair
Check calibration and recalibrate as
necessary (directions on page 4).
Check line seals and joints for
leakage; seal leaks appropriately.
Clean or replace internal metering
components as necessary.
Clean meter chamber; clean or
replace screens and filters in piping.
Install pressure relief valve to allow
high pressure to bleed back to the
tank. Replace meter.
Avoid surge flows by installing a shut-
off valve on outlet of meter; install
meter as close to the pump as
possible, keep piping full of liquid.
Replace meter chamber assembly.
Figure 1
loading