Johnson Controls M9316 Serie Instrucciones De Instalación página 15

Ocultar thumbs Ver también para M9316 Serie:
M9316-xxx-xZ / M9320-xxx-x / M9335-xxx-x
Technical Specifications
Product Code
• Code produit • Produktcode
• Codice prodotto • Código de producto
• Productcode • Produktkod • Kód výrobku
• Kod produktu • Код продукта
• Código de produto • 产品代码 • 製品コード
Control Type
• Type de commande • Steuerungsart • Tipo di comando
• Tipo de control • Besturingstype • Kontrolltyp • Typ řízení
• Typ sterowania • Тип управления • Tipo de controlo • 控制
类型 • 制御タイプ
Power
Transformer
Input
• Entrée • Eingang • Ingresso • Entrada • Ingang • Ingång
• Vstup • Wejście • Вход • Entrada • 输入 • 入力
Impedance
• Impédance • Impedanz • Impedenza • Impedancia
• Impedantie • Impedans • Impedance • Impedancja
• Импеданс • Impedância • 阻抗 • インピーダンス
Feedback
• Rétroaction • Rückmeldung • Ritorno • Realimentación
• Feedback • Feedback • Zpětná vazba • Sprzężenie zwrotne
• Обратная связь • Feedback • 反馈 • フィードバック
Torque
M
Rotation Range
Rotation Time
Compliance
M9320-GUA-1
M9320-GUA-2
Proportional
Nominal AC 230V at
Nominal AC 120V at 60
50/60 Hz: 0.04 A Running
Hz: 0.05 A Running
0(2)...10 VDC, 0(4)...20 mA with field furnished 500 ohm resistor,
Offset: 0...10 VDC, Span: 2...10 VDC
20 Nm (180 lb. in)
Mechanically Limited to 35...95° ±3° in 5° increments
90 s
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical Controls for
Household and Similar Use, Part 1; and UL 60730-2-14: Part 2, Particular Requirements for Electric
Actuators. Plenum Rated (UL 2043). Suitable for use in Other Environmental Air Space (Plenum) in
accordance with section 300.22 (c) of the National Electrical Code.
Canada: UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic Electrical
Controls for Household and Similar Use, Part 1; and CAN/CSA-E60730-2-14, Particular Requirements
for Electric Actuators.
Europe: CE Mark
Johnson Controls declares that these products are in compliance with the essential requirements and
other relevant provisions of the EMC Directive and Low Voltage Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
15
M9335-GUA-1
Proportional
Nominal AC 230V at
50/60 Hz: 0.04 A Running
100k ohm
0(2)...10 VDC
35 Nm (310 lb. in)
150 s
M9335-GUA-2
Nominal AC 120V at 60
Hz: 0.06 A Running
34-636-2502 Rev. B
loading