Technical Specifications
Product Code
• Code produit • Produktcode
• Codice prodotto • Código de producto
• Productcode • Produktkod • Kód výrobku
• Kod produktu • Код продукта
• Código de produto • 产品代码 • 製品コード
Control Type
• Type de commande • Steuerungsart
• Tipo di comando • Tipo de control
• Besturingstype • Kontrolltyp • Typ řízení
• Typ sterowania • Тип управления
• Tipo de controlo • 控制类型 • 制御タイプ
Power
Transformer
Input
• Entrée • Eingang • Ingresso • Entrada
• Ingang • Ingång • Vstup • Wejście • Вход
• Entrada • 输入 • 入力
Impedance
• Impédance • Impedanz • Impedenza
• Impedancia • Impedantie • Impedans
• Impedance • Impedancja
• Импеданс • Impedância
• 阻抗 • インピーダンス
Feedback
• Rétroaction • Rückmeldung • Ritorno
• Realimentación • Feedback • Feedback
• Zpětná vazba • Sprzężenie zwrotne
• Обратная связь • Feedback
• 反馈 • フィードバック
Torque
M
Rotation Range
Rotation Time
Compliance
M9316-AGA-xZ M9316-AUA-1Z M9316-AUA-2Z
On/Off, Floating
Nominal 24 VAC
50/60 Hz 11.6 VA
Nominal 230 VAC
Running
50/60 Hz: 0.07 A
Running
24 VDC Class 2
5.4W Running
AC 100...240 V (AC 85...240 V), 50/60 Hz
100k ohm
16 Nm (144 lb. in)
16s
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical Controls for Household and Similar
Use, Part 1; and UL 60730-2-14: Part 2, Particular Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable
for use in Other Environmental Air Space (Plenum) in accordance with section 300.22 (c) of the National Electrical Code.
Canada: UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic Electrical Controls for Household and
Similar Use, Part 1; and CAN/CSA-E60730-2-14, Particular Requirements for Electric Actuators.
Europe: CE Mark
Johnson Controls declares that these products are in compliance with the essential requirements and other relevant
provisions of the EMC Directive and Low Voltage Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
M9320-HGA-x
On/Off,
Floating
Nominal 120 VAC
24 V ±20%, 50/60 Hz, 5.7 VA
60 Hz: 0.1 A
24 VDC ±10%, 2.1 W
Running
24 VAC ±20%
24 VDC ±10%
4.7k ohm
20 Nm (180 lb. in)
Mechanically Limited to 35...95° ±3° in 5° increments
13
M9335-HGA-x
On/Off,
Proportional
Floating
24 V ±20%, 50/60 Hz, 6.1 VA
24 VDC ±10%, 2.1 W
≥7 VA
0(2)...10 VDC,
0(4)...20 mA with
field furnished 500
24 VAC ±20%
ohm
24 VDC ±10%
resistor
Offset: 0...10 VDC
Span: 2...10 VDC
100k ohm
4.7k ohm
0(2)...10 VDC
35 Nm (310 lb. in)
90 s
150 s
34-636-2502 Rev. B
Proportional
0(2)...10 VDC,
0(4)...20 mA with
field furnished
500 ohm
resistor
Offset: 0...10 VDC
Span: 2...10 VDC
100k ohm
0(2)...10 VDC