Mode
Terminal
l
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4060
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Recommen
Applicable
ded Gauge
Gauge
2
mm
mm
25
6 - 35
16
4 - 25
25
6 - 35
10
2.5 - 16
10
6 - 16
Wire
Terminal Screw
Stripping
Length
*1
Size
2
mm
18
M5
18
M5
18
M5
10
M4
-
M6
10 Attachment
Tightening
Torque
Shape
N∙m (in∙lb)
• ≤ 25 mm
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
2.3 - 2.5
(19.8 - 22)
• ≤ 25 mm
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2
≤
2
≤
295