YASKAWA GA500 Instrucciones De Instalación Y Operación página 39

Ocultar thumbs Ver también para GA500:
Idiomas disponibles

Idiomas disponibles

10 Attachment
10
Attachment
UL Standards
The UL/cUL Mark indicates that this product satisfies stringent safety standards. This mark
appears on products in the United States and Canada. It shows UL approval, indicating that it
has been determined that the product complies with safety standards after undergoing strict
inspection and assessment.
You must use UL Listed or UL Recognized parts for all primary components that are built into
electrical equipment that has UL approval.
This product has been tested in accordance with UL standard UL61800-5-1, and has been
verified to be in compliance with UL standards.
Machines and devices integrated with this product must satisfy the following conditions for
compliance with UL standards.
Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or less as
specified in UL61800-5-1.
Ambient Temperature Setting
Maintain the ambient temperature within the following ranges according to the enclosure type.
• Enclosed wall-mounted type (UL Type 1): -10 °C to +40 °C (14 °F to 104 °F)
• Open chassis type (IP20): -10 °C to +50 °C (14 °F to 122 °F)
Wire the Main Circuit Terminal Block
Wire the main circuit terminal block correctly as specified by the instructions in the manual.
To select the correct wire gauge, refer to
page
268.
Main Circuit Wire Gauges and Tightening Torques
Refer to
Single-Phase 200 V Class on page
Three-Phase 400 V Class on page 303
of the main circuit terminals.
Comply with local standards for correct wire gauges in the region where the drive is used.
WARNING
standards and local safety regulations. The IEC/EN 61800-5-1:2007 standard specifies that you must wire the
power supply to automatically de-energize when the protective ground wire disconnects. If you turn on the
internal EMC filter, the leakage current of the drive will be more than 3.5 mA. You can also connect a protective
ground wire that has a minimum cross-sectional area of 10 mm
and regulations, it can cause serious injury or death.
WARNING
braking resistor, to terminals +1, +2, -, B1, and B2. Failure to obey can cause serious injury or death.
268
Figure 10.1 UL/cUL Mark
for the recommended wire gauges and tightening torques
Electrical Shock Hazard. Make sure that the protective ground wire conforms to technical
Electrical Shock Hazard. Only connect peripheral options, for example a DC reactor or
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Main Circuit Wire Gauges and Tightening Torques on
300,
Three-Phase 200 V Class on page
2
(copper wire). If you do not obey the standards
296, and
loading