The Multi-Way capability is available on all models. Sensors can
easily be wired together for convenient control of a common load.
When wiring this way, only use DW-311 series sensors. Multi-Way
in DW-311 series is not compatible with prior sensor models.
The following principles apply for Multi-Way:
• All units should be on the same phase.
• All units can sense each other's push button events and
respond accordingly.
• All units can sense each other's PIR trigger event. The
response will be determined by the Light Level setting and/or
conditions of the space of the detecting sensor.
• The time delay for all units is defined by the unit with the
smallest time delay.
• All Units can sense each other's dimming events and respond
accordingly.
NOTE: Models with v2 cannot be used with non-v2 models for
multi-way applications.
When used with an ELCU
Wattstopper recommends using an ELCU
device. In this scenario, the DW-311's 0-10VDC
dimming circuit is connected to and alters the light
level of both normally powered lighting loads and
emergency powered lighting loads. The 0-10V
signal is generated by the DW-311.
When Normal Power is available:
When Normal Power is available and the normal
load has been turned off by the sensor, the ELCU
will turn off the Emergency Load as well.
When Normal Power is unavailable:
When normal power to the room controller fails for
any reason, the 0-10VDC dimming circuit in the
DW-311 will revert to an open circuit. Since no
device is controlling the 0-10V circuit, any fixture
that is fed by emergency power will go full on.
Fixtures fed by normal power will of course be off
since there is no power available for their operation.
When no ELCU is used:
In this scenario, emergency lighting cannot be turned
on or off by the sensor, only dimmed. The normal
lighting load has full control. As in the example with
the ELCU, if normal power fails, the emergency
load will go full on. If any Emergency Circuits are
fed or controlled from a panel, they must be located
electrically where fed from a UPS, generator, or other
guaranteed source of power during emergency and
power outage situations.
USING THE DW-311 WITH EMERGENCY LIGHTING
Neutral
(White)
Neutral
(White)
Unswitched
Line (Black)
MULTI-WAY
(DW-311 or DW-311-347 up to 4 sensors)
Line
Purple
Pink
Black
Green
Ground
Neutral
Normal Neutral (White)
Normal
Power
Sense
(Black)
Circle
CUT-OUT
Push to Test
EMERGENCY CIRCUIT
Normal Switch Sense (Red)
Yellow
Unswitched
Line (Black)
Ground
Yellow
Red
Ground
2
Typical Multi-Way Wiring
Yellow
Yellow
traveler
Red
Black
Green
White
Ground
Emergency Power Out (Red)
Emergency Neutral (Gray)
Emergency Power In (Black)
Cut Jumper Loop
to use with
normally closed
Cir.#_______
- Test switch
- Fire alarm panel
- Security panel
- Other
Emergency Line
"Always On"
Emergency Neutral (White)
Neutral
Pink
Red
Normal
Lighting
Neutral (White)
Emergency Line
"Always On"
(Black)
Neutral
Pink
Purple
Normal
Lighting
Neutral (White)
Connect 0-10V
leads to dimming
ballast from one
DW-311 only
Purple
Driver
Pink
or Ballast
Red
White
Purple
Emergency
Lighting
Pink
Purple
Emergency Neutral
(White)
Emergency
Lighting