LEGRAND Wattstopper DW-311 Instrucciones De Instalación

LEGRAND Wattstopper DW-311 Instrucciones De Instalación

Ocultar thumbs Ver también para Wattstopper DW-311:
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 26167 – 01/18 rev. 3
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: DW-311/DW-311-347
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
DESCRIPTION AND OPERATION
The DW Dual Technology Multi-Way Wall
Switch sensors combine advanced passive
infrared (PIR) and ultrasonic technologies
into one unit. The combined technologies
help to eliminate false triggering even in
difficult applications.
• The DW sensor has Multi-Way
• A "walk-through" mode can turn lights
• The DW-311 has one relay with
• DW sensors contain a light level
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the DW flying leads as shown in the wiring diagram
that is appropriate to the DW model and electrical supply. The ground
wire (green) must be fastened to ground for the sensor to work
properly.
3. Attach the sensor to the wall box by inserting screws into the two wide holes on the
top and bottom of the attached metal bracket. Match them up with the holes in the wall
box and tighten. Do not use excessive force when installing the sensor into the
wallbox. Doing so can bend the mounting strap which can affect button operation.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch and
the lights will turn ON. There is a delay due to initial power-up of the sensor that only
occurs during installation.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not included).
Red
White
Black
WARNING: Grounding the violet and gray wires can damage the
unit. Do not apply power to the sensor until all wires are connected or
capped off if the driver is to be installed at a future time.
Wattstopper
Dual Technology 0–10 Volt Wall Switch Occupancy Sensor (version 2)
Interrupteur mural 0–10 Volt avec détecteur de mouvement à double technologie (v2)
Sensor de ocupación con interruptor de pared y tecnología doble de voltaje 0 a 10 (V2)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
available on all models.
off after only 3 minutes, if no activity is
detected after 30 seconds following an
occupancy detection.
dimming control capability and two
buttons to allow control of the dimming.
sensor. If adequate daylight is present,
the sensor holds the load OFF until
light levels drop, even if the area
is occupied. See the Light Level
Adjustment section.
8" flying leads for
#12 – #14 AWG
line, load, ground
and multi-way
connections
Cu Wire Only
Grey
Violet
Yellow
Green
®
Voltages:
DW-311 .................................................120/277 VAC, 50/60 Hz
DW-311-347 .................................................347 VAC, 50/60 Hz
Load Limits:
@120 VAC......... 1000-W tungsten ballast, E-ballast, LED, 1/4 HP
@277 VAC ................... 1200-W ballast, E-ballast, LED, 1/4 HP
@347 VAC .....................................1500W ballast, LED, 1/4 HP
Time Delay Adjustment ..................................................3 to 30 minutes
Walk-Through Mode ....................... 3 minutes if no activity after 30 sec.
Test Mode ............................................. 10 min. with 10-sec. time delay
PIR Adjustment .................................................................... High or Low
Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot), Off
Alerts ........................................................Selectable Audible & Visual
Multi-Way Capability ...............................................................All models
Terminal screw torque ............................................ 16 lbf-in (18 kgf-cm)
High Trim ................................................................................... 6 to 10V
Low Trim ...................................................................................... 0 to 4V
Ramp Up ....................................................................... 1 to 10 seconds
Fade Down ................................................................. 2.5 to 30 seconds
INSTALLATION
Typical Multi-Way Wiring
(DW-311 or DW-311-347 up to 4 sensors)
Strip Gage
1/2"
Line
12.7mm
Violet
Gray
Black
Green
Ground
Neutral
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
DW-311 and DW-311-347 Wiring
Yellow
Black
Line
Green
Ground
Neutral
Yellow
Yellow
traveler
Red
Black
Green
White
Ground
0-10V
Dimming
Violet
Driver
Gray
or Ballast
Red
White
Connect 0-10V
leads to dimming
ballast from one
DW-311 only
Violet
Driver
Gray
or Ballast
Red
White
Tabla de contenido
loading

Resumen de contenidos para LEGRAND Wattstopper DW-311

  • Página 12: Especificaciones

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN DE LA UNIDAD ESPECIFICACIONES Los sensores del interruptor de pared de múltiples vías con Voltajes: tecnología doble DW combinan las tecnologías infrarroja DW-311 ............120/277 V CA, 50/60 Hz pasiva (PIR) avanzada y la ultrasónica en una sola unidad. DW-311-347 ............
  • Página 13: Diagramas De Cobertura

    MÚLTIPLES VÍAS La funcionalidad de múltiples vías está disponible en todos los modelos. Los sensores pueden cablearse fácilmente en conjunto para un control conveniente de la carga común. Cuando cablee de esta manera, solo utilice sensores de la serie DW-311. La función de múltiples vías en la serie DW-311 no es compatible con los modelos anteriores del sensor.
  • Página 14: Encendido Automático

    Encendido automático Con el conmutador selector para bascular 1 en la posición de Apagado, la carga se enciende y se apaga automáticamente según la ocupación. Hay una demora de 5 segundos de reinicio. Si la carga se apaga manualmente, se aplica la operación del ajuste activar/ desactivar en modo de presentación.
  • Página 15 Recorrido El modo de recorrido acorta el tiempo de demora para reducir la cantidad de tiempo en que la carga está encendida después de un breve momento de ocupación como, por ejemplo, volver a la oficina para buscar algo que se olvidó y salir inmediatamente. Si el modo de recorrido se enciende, el sensor DW apaga la carga tres minutos después de que el área esté...
  • Página 16: Configuración Del Conmutador Selector Para Bascular

    Modo de presentación/Desactivar el modo de presentación El modo de presentación es una función del modo de Encendido automático. Cuando el relé se apaga manualmente, el DW mantiene las luces apagadas hasta que no se detecta ningún movimiento durante el tiempo de demora. Con la ocupación subsiguiente, el DW enciende la carga.
  • Página 17: Placas De La Cubierta

    No. 26167 – 01/18 rev. 3 © Copyright 2018 Legrand All Rights Reserved. 800.879.8585 © Copyright 2018 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2018 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

Wattstopper dw-311-347

Tabla de contenido