LEGRAND Wattstopper Manual Del Usuario
Ocultar thumbs Ver también para Wattstopper:

Enlaces rápidos

No: 24178 – 1/19 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPL-201
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
LMPL-201-U is BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go™ operation, adjustment is
optional.
For full operational details, adjustment and more features of the product, see
the DLM System Installation Guide provided with Wattstopper room controllers,
and also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes. Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2
power source only. Do not reclassify and install as Class 1, or Power and
Lighting Wiring.
Line Voltage
(Class 1 wiring)
Plug Load
Controller
To Plug Load
(Class 1 wiring)
To Other
Electrical
Outlets
CONNECTIVITY
The LMPL-201 communicates to all other DLM
devices connected to the DLM Local Network.
Connections shown are for example only. The
low voltage LMRJ cables can connect to any
DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG.
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
PLACEMENT EXAMPLES
J-Box
Switch
Ceiling Mount
Occupancy
Sensor
Corner Mount
Switch
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT –
IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Wattstopper
DLM Enhanced Digital Single Relay Plug Load Controller
Relais numérique simple amélioré – Contrôleur de prises DLM
Controlador DLM de un solo relé para receptáculo de CA
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
Input Voltage .................................................... 120VAC, 50/60Hz
Load Rating:
Maximum Duplex Receptacle Rating ...............120VAC, 20A
Connection to the DLM Local Network .................... 4 RJ-45 ports
DLM Local Network characteristics when using LMPL-201 room
controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 and/or LMPL-201controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 158°F (0° to 70°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
Line Voltage
(Class 1 wiring)
To Other
Electrical
Outlets
Ceiling Mount
Sensor
Sensor
Dimmer
LMPL or
LMRC series
Room Controller
®
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Line Voltage
(Class 1 wiring)
J-Box
Plug Load
To Lighting
Controller
Load
(Class 1 wiring)
To Plug Load
(Class 1 wiring)
Line
DLM Local Network
Voltage
Low Voltage
LMRJ Cables
Plug Load
Controller
Deep J-Box
Black wire w/white stripe to Unswitched Receptacle
Room
Controller
J-Box
Switch
Ceiling Mount
Occupancy
Sensor
Earth Ground/Green wire
Line/Hot
Black wire
Neutral
White wire
Loads
Ground
Switched
Receptacle
Ground
Unswitched
Receptacle
Red wire to Switched Receptacle
loading

Resumen de contenidos para LEGRAND Wattstopper

  • Página 1 For full operational details, adjustment and more features of the product, see Operating Temperature ....32° to 158°F (0° to 70°C) the DLM System Installation Guide provided with Wattstopper room controllers, Storage Temperature ....23° to 176°F (-5° to 80°C) and also available at www.legrand.us/wattstopper.
  • Página 2 MOUNTING THE CONTROLLER ATTACHING LMRJ LOW VOLTAGE CABLES The plug load room 4” square deep controller mounts as the J-box cover for a four square deep junction box. It is equipped with a lash and Hook hook to hang the controller Lash from a j-box cover tab while connecting the...
  • Página 3 Pour connaître tous les détails opérationnels, les réglages et les fonctions supplémentaires du produit, consultez le guide d'installation du système Duplex maximum réceptacle note .......120VAC , 20A DLM fourni avec les combinateurs Wattstopper et aussi disponible au Branchement au réseau local DLM ........4 ports RJ-45 www.legrand.us/wattstopper.
  • Página 4 MONTAGE DU CONTRÔLEUR FIXATION DES CÂBLES BASSE TENSION DE Le contrôleur de prises Boîte de jonction LMRJ profonde (4 po) s'installe comme un couvercle de boîte de jonction profonde carrée de dix centimètres (quatre pouces). Il est équipé Crochet d'une lanière et d'un Lien crochet pour suspendre le régulateur depuis l'attache...
  • Página 5: Especificaciones

    Guía de instalación del sistema DLM que Capacidad máxima para receptáculo dúplex .....120VAC , 20A se proporciona con los controladores de habitación Wattstopper; Conexión a la red local DLM ........... 4 puertos RJ-45 también está disponible en www.legrand.us/wattstopper.
  • Página 6 EJEMPLOS DE UBICACIÓN Voltaje de línea (Cableado Clase 1) Voltaje de línea (Cableado Clase 1) Voltaje de línea (Cableado Clase 1) Controlador de habitación Caja de conexiones Caja de Controlador de Caja de conexiones conexiones habitación A cargas de iluminación Controlador de (Cableado Clase 1) habitación...
  • Página 7 FUNCIONAMIENTO DE PLUG N’ GO (PNG) El controlador de receptáculo de CA LMPL-201 es controlado LED azul ENCENDIDO cuando automáticamente por todos los sensores de ocupación de la red local DLM. el circuito del receptáculo está Después de que transcurre el tiempo de demora del sensor de ocupación, ACTIVADO.
  • Página 8 (5) years. There are no obligations pour une période de cinq (5) ans. Wattstopper de obra por un período de cinco (5) años. No or liabilities on the part of Wattstopper for ne peut être tenu responsable de tout dommage...

Este manual también es adecuado para:

Lmpl-201