Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 29259 – 11/20 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: DSW-301-347/DSW-302-347
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
DSW-301-347
The DSW Dual Technology Multi-Way Wall Switch sensors combine advanced passive infrared (PIR) and ultrasonic technologies into
one unit. The combined technologies help to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load ON, and hold it ON as long as either or both technologies detect occupancy.
It allows for up to 4 sensors to be connected to the same circuit. The first sensor to detect occupancy will turn ON all the lights that are
connected to the same circuit. After the room is unoccupied, the last sensor that detected occupancy turns OFF all the lights once the
time delay has expired. The occupant can turn OFF the load at any time by pressing the ON/OFF button of any sensor that is connected
to the circuit. A "walk-through" mode can turn lights OFF after only 3 minutes if no activity is detected after 30 seconds following an
occupancy detection.
The DSW-301-347 has one relay and one ON/OFF button. The DSW-302-347 contains two relays and two ON/OFF buttons to allow control
of one or two loads independently. Pressing a button toggles the state of the corresponding relay. Optional Neutral is also available on both
models.
DSW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if
the area is occupied. In the DSW-302-347, light level only affects the load on Relay 2. Users can override this function by pressing the
ON/OFF button. See the Light Level Adjustment section.
Turning Load(s) ON (ON Mode)
The relays are programmed independently for either Auto ON or Manual ON. In either mode, the load can be turned ON or OFF using
the ON/OFF button.
Manual ON
DIP 8 ON for Relay 1
DIP 9 ON for Relay 2
Auto ON
DIP 8 OFF for Relay 1
DIP 9 OFF for Relay 2
DSW-302-347
DESCRIPTION AND OPERATION
With an ON Mode DIP switch in the ON position, the occupant must press the ON/OFF button to turn ON
the load. The sensor keeps the load ON until no motion is detected for the selected time delay. There is a
30 second re-retrigger delay. If occupancy is detected during the delay, the sensor turns the load back ON.
After the re-trigger delay elapses the ON/OFF button must be pressed to turn ON the load.
With an ON Mode DIP switch in the OFF position, the load turns ON and OFF automatically based on
occupancy. If the load is turned OFF manually, Presentation Mode operation applies. This prevents the load
from turning ON automatically after it was deliberately turned OFF. Pressing the button to turn lights ON
returns the sensor to Auto ON mode.
Wattstopper
Dual Technology Multi-Way Wall Switch Occupancy Sensor
Interrupteur mural multiple à double technologie Détecteurs de mouvement
Interruptor de pared de múltiples vías con Sensores de ocupación con
doble tecnología
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage ............................................................................347 VAC, 50/60 Hz
Load Limits for relay 1 ...................................... 1500-W ballast, LED, 1/4 HP
Load Limits for relay 2 ...................................... 1500-W ballast, LED, 1/6 HP
Time Delay Adjustment ......................................................... 5 to 30 minutes
Walk-Through Mode ...............................3 minutes if no activity after 30 sec.
Test Mode ...................................................... 10 min. with 5 -sec. time delay
PIR Adjustment ............................................................................High or Low
Ultrasonic Adjustment ........................................... Minimum to Maximum, Off
Frequency ...................................................................................40 kHz
Light Level Adjustment .............................................................. 8fc to 180+fc
Alerts .................................................................. Selectable Audible & Visual
Optional Neutral ......................................................................... Both models
Multi-Way Capability ................................................................... Both models
Terminal screw torque .................................................... 16 lbf-in (18 kgf-cm)
®
SPECIFICATIONS
loading

Resumen de contenidos para LEGRAND DSW-301-347

  • Página 1 The DSW-301-347 has one relay and one ON/OFF button. The DSW-302-347 contains two relays and two ON/OFF buttons to allow control of one or two loads independently. Pressing a button toggles the state of the corresponding relay. Optional Neutral is also available on both models.
  • Página 2 Model # Relay Default ON DIP switch Setting Mode DSW-301-347 Manual ON DSW-302-347 Auto ON Manual ON Presentation Mode Presentation Mode is a feature of the Auto ON mode.When both relays are manually turned OFF the DSW holds the lights OFF until no motion has been detected for the duration of the Time Delay.
  • Página 3 COVERAGE PATTERNS Coverage testing has been performed according to the NEMA WD 7 guideline. For Top View best performance, use in spaces not larger than 18’ x 15’. Major motion Major motion PIR Sensor Minor motion Minor motion Ultrasonic The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field Coverage Coverage of view.
  • Página 4 The Multi-Way capability is available on all models. Sensors can easily Typical Wiring be wired together for convenient control of a common load. When wiring (DSW-301-347 up to 4 sensors) this way, only use 300 series sensors. Multi-Way in 300 series is not compatible with prior sensor models.
  • Página 5 SENSOR OPERATING MODES Sensor #1 Sensor #2 Light Fixture The load turns ON and OFF automatically based on occupancy detection by either one of the sensors. Auto-ON Auto-ON The sensors keep the load ON until no motion is detected and will use the time delay of the sensor with the lowest value.
  • Página 6 2. Verify that the sensor is mounted at least six feet (2 meters) away from any heating/ventilating/air conditioning device that may cause false detection. Verify that there is no significant heat source (such as a high wattage light bulb) mounted near the sensor. 3.
  • Página 7 Le DSW-301-347 dispose d’un relais et d’un bouton MARCHE/ARRÊT. Le DSW-302-347 comprend deux relais et deux boutons MARCHE/ARRÊT pour permettre un contrôle indépendant d’une ou de deux charges. La pression sur un bouton fait basculer l’état du relais correspondant.
  • Página 8 Test/20 min. Le mode test, avec une temporisation courte de 5 secondes, est lancé lorsque les interrupteurs DIP 1 (DIP 1 & 2 OFF) et 2 sont ARRÊT. Il s’annule automatiquement au bout de dix minutes ou lorsque vous paramétrez une temporisation fixe.
  • Página 9 PORTÉES Le test de portée a été réalisé conformément à la norme NEMA WD 7. Pour un meilleur fonctionnement, utilisez l’unité dans des pièces ayant une taille maximale de 5,5 m x 4,6 m (18 pi x 15 pi). Vue du haut Détecteur IRP Mouvement Mouvement...
  • Página 10 • La temporisation de toutes les unités est définie par l’unité possédant la temporisation la plus courte. Câblage standard Câblage biphasé (DSW-301-347 - jusqu’à 4 détecteurs) Neutre Circuit Circuit 1...
  • Página 11 (5) =MARCHE =ARRÊT DSW-302 Modèle DSW-302-347 illustré. Le DSW-301-347 dispose d'un seul bouton et le potentiomètre d'ajustement de la sensibilité aux ultrasons est dans une position légèrement différente. MODES DE FONCTIONNEMENT DU DÉTECTEUR Détecteur 1 Détecteur 2 Luminaire...
  • Página 12 Les lumières ne s’ÉTEIGNENT pas 1. Il peut y avoir une temporisation de 30 minutes maximum après la dernière détection de mouvement. Pour vous assurer d’un fonctionnement correct, réglez l’interrupteur DIP 1 sur MARCHE, puis réinitialisez les interrupteurs 1 et 2 sur ARRÊT pour démarrer le mode test.
  • Página 13 30 segundos de una detección de ocupación. El modelo DSW-301-347 tiene un relé y un botón de Encendido y Apagado. El DSW-302-347 contiene dos relés y dos botones de Encendido/Apagado para permitir el control de una o dos cargas independientemente. Presionar un botón alterna el estado del relé...
  • Página 14 El modo de presentación es una función del modo de activación automática . Cuando ambos relés se desactivan manualmente, el sensor DSW mantiene las luces desactivadas hasta que no se detecta movimiento durante la duración del tiempo de retardo. Con la ocupación subsiguiente, el DSW enciende la carga.
  • Página 15 DIAGRAMAS DE COBERTURA La prueba de cobertura se realizó de acuerdo con los lineamientos NEMA WD 7. Para Vista superior un mejor desempeño, utilícelo en espacios no superiores a 5,5 x 4,5 m (18’ x 15’). Movimiento Movimiento mayor mayor Sensor del PIR Movimiento Movimiento...
  • Página 16 • El tiempo de retardo para todas las unidades está definida por la unidad con el menor tiempo de retardo. Cableado típico Cableado de dos niveles (DSW-301-347 – hasta 4 sensores) (DSW-302-347 – hasta 4 sensores) Línea Línea...
  • Página 17 DSW-301 =Activado = Desactivado DSW-302 Se muestra el DSW-302-347. El DSW-301-347 tiene un único botón y el potenciómetro de ajuste de sensibilidad ultrasónica se encuentra en una posición ligeramente distinta. MODOS DE FUNCIONAMIENTO DEL SENSOR Sensor N.° 1 Sensor N.° 2 Accesorio de iluminación...
  • Página 18 No. 29259 – 11/20 rev. 1 © Copyright 2020 Legrand All Rights Reserved. 800.879.8585 © Copyright 2020 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2020 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

WattstopperDsw-302-w