Configuration - BFT RIGEL 5 Instrucciones De Uso

Central universal para el control de uno o dos motores
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
ENGLISH
7) TERMINAL BOARD CONNECTIONS (Fig.3)
WARNINGS - For wiring and installation operations, refer to the current
standards and good technical principles.
Wires powered at different voltages must be physically separated, or suitably
insulated with at least 1 mm extra insulation. The wires must be clamped by
an extra fastener near the terminals, for example by bands.
WARNING! For connection to the mains, use a multipolar cable with a
2
minimum of 3x1.5mm
cross section and complying with the previou-
sly mentioned regulations. For example, if the cable is out side (in the
open), it has to be at least equal to H07RN-F, but if it is on the inside
(or outside but placed in a plastic cable cannel) it has to be or at least
egual to H05VV-F with section 3x1.5mm
JP1
1
GND terminal.
2-3
230Vac±10%, 50-60Hz power supply (2 neutral, 3 phase).
JP2
4-5-6
Motor connection 1 (delayed opening), terminals 5-6 for motor
drive, terminal 4 common.
5-14 (JP12) Motor capacitor connection 1.
7-8-9
Motor connection 2 (delayed closing), terminals 8-9 for motor
drive, terminal 7 common.
8-15 (JP12) Motor capacitor connection 2.
N.B. If only one motor is used, use motor output 2 and configure
logic "1 active motor".
10-11
230Vac output for blinker light (40W max) and EBP 230V mo-
delelectric lock.
WARNING! If the SSR5 auxiliary board is used to preheat the
motors, move the JP2-5 connection to the JP2-6 terminal of
the SSR5 board.
12-13
230Vac output for zone/courtesy/blinking lights, 150W max. To
set the output, refer to paragraph 9.2 Logic Menu ("courtesy
light" and "blinking light").
JP12
14
Motor 1 capacitor connection.
15
Motor 2 capacitor connection.
16-17
Light/alarm output with free n.o. contact, to pilot stair-light timer
or alarm signal for failed gate closure. As a light it commands an
impulse (impulse time 1 s) at the start of the operation, as an
alarm it lights up if the gate remains open for twice the TCA setting
(inhibited by dwell TCA (automatic closing time) logic = 0).
JP3
18-19
N.O. output (3W max) for 2nd radio channel or for gate-open
warning light.This light is off when the gate is closed, flashing on
closing and turned on if the gate is opening or already open.
20-21
Output 24V ac (1A max) powers accessories and photoreceivers.
20-44
Output 24V AC powers phototransmitters.
22-23
12Vdc electric lock output, with click (3-second impulse), or
suction.
24-25
Antenna input for radio receiver board (24 signal, 25 braid).
JP4
26-27
Internal Start Pushbutton (n.o.). Internal Start command for
traffic light.
27-28
Start Pushbutton (n.o.). Parallel to radio receiver relay (CH1).
External Start command for traffic light.
27-29
Pedestrian pushbutton (n.o.). Activation takes place on motor 2;
moreover, if the opening cycle has started (not from pedestrian
pushbutton), the pedestrian control has the same effect as a
Start command.
30-31
Open Pushbutton (n.o.).
30-32
Close Pushbutton (n.o.).
33-34
Lock pushbutton (n.c.). If not used, leave the jumper con-
nected.
35-36
Input for ADMAP (dangerous movement area accessible to
the public) photocell contact (n.c.). If this is not used, leave the
jumper connected.
With ADMAP Photocell Logic = 0: In case of activation before
opening, movement is prevented; if activation occurs during
opening, movement is stopped and the opening manoeuvre is
resumed after release.
With ADMAP Photocell Logic =1:Photocell excluded on opening.
The opening movement takes place even when an obstacle is
present.
N.B.RegardlessoftheADMAPPhotocellLogic,photocellactivation
during the closing manoeuvre causes stopping and reopening.
36-37
If not used, leave the jumper connected. Input for photocelledge
contact on opening SAFE OP(n.c.). In case of activation during
opening, the gate is stopped and partly closed.If not used, leave
the jumper connected.
38-39
Opening limit switch for motor 1 (n.c.). If not used, leave the
jumper connected.
14 -
RIGEL 5 - Ver. 02
INSTALLATION MANUAL
2
.
39-40
Closing limit switch for motor 1 (n.c.). If not used, leave the
jumper connected.
41-42
Opening limit switch for motor 2 (n.c.). If not used, leave the
jumper connected.
42-43
Closing limit switch for motor 2 (n.c.). If not used, leave the
jumper connected.
JP5
20(JP3)-44 24V output for transmitters.
45-46-47
Connection with tested safety devices (see Fig. from 7 to 21).
48-49-50
Connection with tested safety devices (see Fig. from 7 to 21).
JP6
51-52
Clock input (n.o.). If the connected contact is open (n.o.), the
leaves close and get ready for normal operation. If the contact
is closed (n.c.), the leaves open and stay open until the contact
reopens.
52-55
Input for photocelledge contact on closing SAFE CL (n.c.). In
case of activation during closing, the gate is stopped and partly
reopened. If not used, leave the jumper connected.
53
Photocell test input (PHOT-FAULT).
54
Safety edge/opening photocell test input (BAR-FAULT).
56
Closing photocell test input (PHOT CL-FAULT).
JP7
Radio receiver board connector.
JP8
Serial connection board connector (SCS1).
JP9
Traffic-light / Preheating SSR5 board connector.
8) PROGRAMMING
The control unit is provided with a microprocessor and supplied with operation
parameters set by the manufacturer. The predefined parameters can only
be changed by means of the UNIPRO programmer.
Before modifying the parameters, carefully read the instructions relating to
the UNIPRO programmer, and proceed as described below.
Connect the UNIPRO programmer to the control unit through the UNIFLAT
accessory (See fig.5). Enter the "CONTROL UNIT" menu and the "PARA-
METERS" submenu, and scroll the display screenfuls using the up/down
arrows, then set the numerical values of the parameters listed below. For
the function logics, refer to the "LOGIC" submenu. When using the incorpo-
rated programmer for programming, make reference to Fig. A and B and the
"Configuration" paragraph. Here is a list of the meanings and values which
can be ascribed to each parameter.

9) CONFIGURATION

The display programmer is used to set all the RIGEL 5 control panel functions.
The programmer is provided with three pushbuttons for menu scrolling and
function parameter configurations (Fig. 2):
+
menu scrolling/value increment key
-
menu scrolling/value reduction key
OK
Enter (confirm) key
The simultaneous pressure of the + and – keys is used to exit the active
menu and move to the preceding menu.
If the + and – keys are pressed simultaneously at the main menu level (para-
meters, logics, radio, language, autosetting), programming is exited and the
display is switched off (The END message will be displayed).
The modifications made are only set if the OK key is subsequently pressed.
When the OK key is pressed for the first time, the programming mode is
entered.
The following pieces of information appear on the display at first:
-
Display Software version
-
Control unit Software version
-
Number of total manoeuvres carried out (the value is expressed in hun-
dreds, therefore the display constantly shows 0000 during the first cent
manoeuvres).
-
Number of manoeuvres carried out since the latest maintenance operation
(the value is expressed in cent, therefore the display constantly shows
0000 during the first hundreds manoeuvres).
-
Number of memorised radio control devices.
When the OK key is pressed during the initial presentation phase, the first
menu (parameters) can be accessed directly.
Here follows a list of the main menus and the respective submenus available.
The predefined parameter is shown between square brackets [ 0 ].
The writing appearing on the display is indicated between round brackets.
Refer to Figures A and B for the control unit configuration procedure.
9.1) Parameter Menu (PARAM)
1 - Operation time motor 1(work. t. mot. 1 ) [60s]
Enter the numerical value corresponding to the working time from 3 to
180 seconds for motor 1.
1 - Operation time motor 2 (work. t. mot. 2 ) [60s]
Enter the numerical value corresponding to the working time from 3 to
180 seconds for motor 2.
2 - Pedestrian operation time (ped. t. ) [6s]