Rubber gasket must be mounted (factory supplied), otherwise
water leakage may be caused.
Note the location of shut-off valves, and the direction of shut-off
valves and drain valve, which are essential to maintenance.
Screw up shut-off valves by using two wrenches.
(2) Additional water strainer
Provide a 50 mesh or more water strainer at the water inlet
side of water piping. Otherwise, damage to the plate heat
exchanger may occur. In the plate heat exchanger, water flows
through a narrow space between the plates. Therefore, there
is a possibility that freezing or corrosion may occur if foreign
particles or dust clog the flow of water between the plates.
This is not required when cooling mode is not used.
Water Flow Direction →
The water piping connection needs to be completed after
flushing the water system.
8.3.2 Drain pipes connection
For a correct drainage, connect the drain pipe for the unit to
the general draining system.
Water Strainer
(50 mesh or more recommended)
Step 1 Insert the drain
pipe for the safety valve
into the drain pipe for the
indoor unit.
valve
● The safety valve is activated when water pressure
reaches 3 bar.
Insert the drain pipe of
indoor unit completely to
the end of the hose
connection.
of indoor unit
3
Insulate the drain pipe after connecting
the drain hose.
Check if water flows without obstruction.
Drain pipe is not needed if cooling operation is not used.
The recommended drain pipe of the indoor unit is polyvinyl
chloride pipe with a 1 inch inner diameter.
Ensure that the drain pipe is firmly fixed through the clamp,
otherwise it may cause water leakage.
The drain pipe should always be open to the atmosphere, free
of frost and in continuous slope to the down side in case that
water leakage exists.
13
PIPING WORK
.