Cleaning or replacing the flowmeter
Before carrying out the following instructions it is advisable to protect the room and the boiler's electrical box
A
against accidental water spillage.
5
Disconnect the power supply and turn off the gas cock ahead of the valve.
Remove the diverter valve connector
Close the cold water inlet and turn on the DHW system faucets
Release the fork "4" and remove the flowmeter assembly "5".
The flowmeter components can thus be cleaned (see fig. 49 and fig. 50) or replaced.
Wash the filter with clean water.
EN
4
fig. 48- Flowmeter
fig. 49
cod. 3541N270 - Rev. 02 - 11/2017
1 - Flow-rate restrictor
2 - Fan
3 - Filter
4 - Clip
5 - Flowmeter
1
2
3
Lubricate the flowmeter gaskets with silicone grease.
fig. 50