Lamborghini Caloreclima EM 26-E Manual Para La Instalación Y El Mantenimiento página 38

Ocultar thumbs Ver también para EM 26-E:
Idiomas disponibles
  • ES

Idiomas disponibles

CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a drop in combustion air pres-
sure. It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure, checking that CO values do not
exceed 10,000 p.p.m..
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to shut it down if the gas pressure
falls below the minimum required level. This setting should be 40% lower than the gas pressure obtained with the burner
operating at maximum delivery.
PRESSURE SWITCH
Type: LGW 3 A2
LGW 3 A2P
LGW 10 A2P
GW 150 A2
GW 150 A5
Remove the cover and
adjust dial A
MODEL
EM 16-E
EM 26-E
CHECKING CONTROL BOX IONIZATION CURRENT
The minimum value of 3 A should be observed,
and large oscillations are to be avoided.
P r e s s u r e
connector
Air pressure switch
Setting range mbars
DUNGS type
LGW 3 A2
LGW 3 AP
Gas pressure switch
DUNGS type
0,4 - 3
GW 150 A2
GW 150 A5
0,4 - 3
MICROAMPEREMETER CONNECTION
- 38
-
Setting range mbars
5 - 150
5 - 120
loading

Este manual también es adecuado para:

Em 16-e